| 2007-12-03 13:57:03 | |
| | ** DENIED 2ND REVIEW ** |
| | |
| | ** PLEASE SEE MOST COMMENTS FROM PREVIOUS REVIEW |
| | REMAIN. |
| | |
| | 1) NOTE: PLEASE SUBMIT TWO COMPLETE SETS OF PLANS AND |
| | DOCUMENTS ALL ATTACHED INTO EACH SET RESPECTIVELY. |
| | PLEASE SEE ALL DOCUMENTS FOR EACH TRADE ARE DIVIDED AND |
| | NOT IN SETS. |
| | FBC 106.3.1, 106.1.2 |
| | |
| | 2) NOTE: PLEASE SEE NOTES FROM PREVIOUS REVIEW WHICH |
| | MOST STILL REMAIN. |
| | NEED TO KNOW THE OCCUPANCY OF PROJECT. |
| | NEED PLANS SHOWING LOCATION(S) FOR ALL EQUIPMENT, |
| | SERVICE EQUIPMENT ETC. |
| | NEED TO SHOW ALL RELEVANT CODES. |
| | NEED TO HAVE THE DESIGNER OF RECORD. |
| | ETC. |
| | |
| | ** PLEASE SEE THE NOTES BELOW ARE COPIED FROM PREVIOUS |
| | REVIEW. |
| | |
| | ** DENIED** |
| | |
| | 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS |
| | WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES |
| | PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-110 ( FBC CHAPTER 27 REFERENCED. |
| | |
| | 2) NOTE: PLEASE SUBMIT LOADS ON THIS EXISTING/NEW |
| | GENERATOR TO BE INSTALLED. |
| | PLEASE PROVIDE INFORMATION IF THIS UNIT FEEDS ANY |
| | EMERGENCY LIFE SAFETY SYSTEMS OR LEGALLY REQUIRED |
| | SYSTEMS.700, 701, |
| | PLEASE SEE 700.12B3, 701.11B3 AS ANY LIFE SAFETY, OR |
| | LEGALLY REQUIRED SYSTEMS FED BY THIS UNIT WILL REQUIRE |
| | *ON-SITE* FUEL MEETING THE MINIMUM LOADS FOR THE |
| | MINIMUM SPECIFIED TIMES DEPENDING ON INSTALLATION. WHAT |
| | ARE THE INTENDED LOADS? 701.5, 700.5, 702.5 |
| | |
| | 3) NOTE: PLEASE SEE AS OCCUPATION FOR THE DESIGNATED |
| | GENERATOR IS NOT KNOWN, PLEASE BE AWARE OF HOUSE BILL |
| | 7121 FOR STAND-BY SYSTEMS AND REQUIRED ON-SITE FUEL. |
| | |
| | 4) NOTE: OK |
| | |
| | 5) NOTE: PLEASE SEE FS 481.229 AND 471.003, EVEN WHEN |
| | THE SCOPE OF WORK IS NOT REQUIRED TO BE DONE BY AN |
| | ARCHITECT OR ENGINEER, THE SCOPE OF WORK STILL REQUIRES |
| | THE DESIGN TO CONTAIN THE PRINTED NAME AND SIGNATURE OF |
| | THE PERSON TAKING RESPONSIBILITY OF SAID PLANS. |
| | 106.3.5, 106.1.2 |
| | |
| | 6) NOTE: PLEASE SEE POSSIBLE BUILDING COMMENTS WITH |
| | RESPECT TO ANY FLOOD ZONE WHICH WOULD REQUIRE THE |
| | GENERATOR TO BE MOUNTED 6INCHES ABOVE BFE> (IF IN FLOOD |
| | ZONE). |
| | |
| | 7) NOTE: PLEASE SUBMIT TWO COPIES OF ALL DOCUMENTS |
| | SPECS/CUT SHEETS. |
| | FBC 106.1 |
| | |
| | 8) NOTE: PLEASE PROVIDE SITE/OVERVIEW OF THE LOCATION |
| | OF THIS UNIT AND ALL RELEVANT EQUIPMENT. |
| | PLEASE SEE 225.31-225.39 FOR REQUIRED DISCONNECTING |
| | MEANS FOR FEEDERS FROM THE GENERATOR. |
| | AS NO SITE PLANS AND OTHER NEEDED INFORMATION WAS |
| | SUBMITTED NO REVIEW OF THIS FOR CODE COMPLIANCE CAN BE |
| | DONE. |
| | |
| | ** PLEASE SEE COMMENTS FROM OTHER TRADES WHICH WILL |
| | AFFECT PLANS, SUBMITTED DOCUMENTS AND ELECTRICAL |
| | PLANS. |
| | |
| | ** PLEASE KNOW AS NOT ALL INFORMATION WAS SUBMITTED FOR |
| | REVIEW AND DUE TO COMMENTS ABOVE, THERE MAY VERY WELL |
| | BE NEW COMMENTS ON THE FOLLOWING REVIEW. |
| | NOTES CAN ONLY BE GIVEN BASED ON PLANS/DOCUMENTS |
| | SUBMITTED. |
| | |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |