| 2007-10-26 14:53:54 | DENIED |
| | REFERENCE: |
| | ** FBC-2004 WITH 05 & 06 REVISIONS, FUEL GAS. |
| | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| | REQUIREMENTS. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE (FAC). |
| | ** FLORIDA STATUTES (FS). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | CONTRACTOR INFORMATION |
| | NOTE: GAS PERMIT REQUIRED. GAS CONTRAC- |
| | TOR TO SUBMIT PLANS WITH PERMIT APPLICA- |
| | TION. ALL GAS INSPECTIONS TO BE COMPLETE |
| | BEFORE FINAL GEN/COM INSPECTION. |
| | |
| | ******IMPORTANT INFORMATION****** |
| | AS OF 8/25/06 GENERATOR (GEN/RES AND |
| | GEN/COM) PERMIT APPLICATIONS SHALL NOT |
| | BE ACCEPTED UNLESS THE ELECTRICAL INFOR- |
| | MATION AND GAS (OR DIESEL) INFORMATION |
| | IS ALL SUBMITTED AT THE SAME TIME. THE |
| | GENERATOR, ELECTRICAL AND GAS/DIESEL IN- |
| | FORMATION WILL BE ROUTED TOGETHER. THIS |
| | WILL ENSURE THAT ALL OF THE INFORMATION (PARTICULARLY |
| | THE MANUFACTURER'S SPECI- |
| | FICATIONS AND INSTALLATION INSTRUCTIONS) |
| | ARE AVAILABLE TO ALL PLAN REVIEWERS. |
| | |
| | 1. PER FBC-2004 CHAPTER 1, SECTION 106.1: SUBMITTAL |
| | DOCUMENTS. CONSTRUCTION |
| | DOCUMENTS, SPECIAL INSPECTION AND |
| | STRUCTURAL OBSERVATION PROGRAMS, AND |
| | OTHER DATA SHALL BE SUBMITTED IN TWO OR |
| | MORE SETS WITH EACH APPLICATION FOR A |
| | PERMIT. |
| | |
| | 2. PROVIDE TWO (2) COPIES OF A SITE PLAN OR SURVEY |
| | THAT CLEARLY INDICATES THE PROPOSED LOCATION OF THE |
| | GENERATOR INDICATING ALL DIMENSIONS FROM PROPERTY LINES |
| | AND ADJACENT DWELLING STRUCTURES. |
| | |
| | 3. PROVIDE MANUFACTURER'S SPECFICATIONS FOR THE |
| | PROPOSED GENERATOR INDICATING RECOMMENDED SET BACKS |
| | FROM STRUCTURES. |
| | |
| | 4. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE, CORRESPONDING |
| | LENGTHS, AND THE TYPE OF PIPE MATERIAL BEING USED ON |
| | THE EXISTING SYSTEM PER FBC-2004 FUEL GAS CODE. |
| | |
| | 5. WHAT IS THE TYPE OF GAS BEING USED? (LP OR |
| | NATURAL) |
| | |
| | 6. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | **NOTE: WHAT IS THE BTU LOAD OF THE EXISTING |
| | GENERATOR? |
| | |
| | 7. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | **NOTE: WHAT IS THE LONGEST LENGTH OF THE EXISTING GAS |
| | SYSTEM? |
| | |
| | 8. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | **NOTE:WHAT IS THE DELIVERY PRESSURE OF THE EXISTING |
| | GAS SYSTEM? |
| | |
| | 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO |
| | VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | **NOTE: IF GAS DELIVERY PRESSURE IS GREATER THAN 2 PSI |
| | PLEASE SUBMIT TWO (2) COPIES OF THE MP REGULATORS BEING |
| | USED WITH THE MAKE, MODEL NUMBER, BTU LOAD CAPACITY, |
| | AND A LISTING FROM A NATIONALLY RECOGNIZED TESTING |
| | LABORATORY. |
| | |
| | 10. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | |
| | 11. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES |
| | PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 6.6.1. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL: [email protected] |