| 2007-10-20 09:47:03 | BUILDING PLAN REVIEW |
| | PERMIT: 07090466 |
| | ADD: 1041 45TH STREET |
| | CONT: NEUTRON ELECTRIC |
| | TEL: (561)201-5005 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1A)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS, |
| | REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR |
| | REVIEW FOR PERMIT. |
| | IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF |
| | YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A |
| | THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID |
| | DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1* |
| | /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH |
| | ADMINISTRATIVE CODE. |
| | |
| | 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 |
| | DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN |
| | THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF |
| | MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY |
| | WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE |
| | SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS |
| | A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS |
| | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT |
| | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 1E) PLANS SUBMITTED FOR PERMIT APPLICATION (FIRST TIME |
| | REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE |
| | 2004 FBC BUILDING WITH THE2007 REVISIONS. |
| | |
| | 2) MISSING INFORMATION ON PLAN IN REGARDS TO WIND: 2004 |
| | FL. BLD CODE 1603.1.4 THE FOLLOWING INFORMATION RELATED |
| | TO WIND SHALL BE SHOWN ON THE CONSTRUCTION DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | |
| | 3) 2004 FBC 1609.1.3 PLEASE PROVIDE INFORMATION ON THE |
| | ANCHORAGE THE GENERATOR TO RESIST THE MOMENT OF |
| | OVERTURNING, UPLIFT AND SLIDING. |
| | GENERATOR SLAB & ANCHOR REQUIREMENT PLEASE PROVIDE |
| | SIZE OF GENERATOR(WXL),PLUS PROVIDE PLANS WITH THE |
| | INFORMATION DEPICTING HOLD DOWN BRACKETS, TYPE OF |
| | FASTENER, AND THE MINIMUM EDGE DISTANCE THE DEVICE |
| | REQUIRES WITHOUT LOAD REDUCTION. |
| | |
| | THE NEW SLAB AND HOLD DOWN DETAILS: 104.2.1* ALL |
| | INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING |
| | DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR THE DESIGN. PLEASE SEE ELECTRICAL |
| | COMMENTS FOR ADDITIONAL INFORMATION REQUIRED FOR THE |
| | DESIGNER. FL S S 481.229 (ARCHITECT)OR FL S S 471.003 |
| | (ENGINEER). |
| | |
| | |
| | 4) PLEASE PROVIDE A SITE PLAN INDICA PROVIDE PLANS |
| | ENOUGH TO VERIFY LOCATION OF GENERATOR VERSES BUILDING |
| | OPENINGS WINDOWS, DOORS OR SOFFIT TYPE VENTS, ETC. |
| | |
| | MECHANICAL CODE |
| | 804.3.4 HORIZONTAL TERMINATIONS. HORIZONTAL |
| | TERMINATIONS SHALL COMPLY WITH THE FOLLOWING |
| | REQUIREMENTS: |
| | 1.WHERE LOCATED ADJACENT TO WALKWAYS, THE |
| | TERMINATION OF MECHANICAL DRAFT SYSTEMS SHALL BE NOT |
| | LESS THAN 7 FEET (2134 MM) ABOVE THE LEVEL OF THE |
| | WALKWAY. |
| | 2.VENTS SHALL TERMINATE AT LEAST 3 FEET (914 MM) |
| | ABOVE ANY FORCED AIR INLET LOCATED WITHIN 10 FEET (3048 |
| | MM). |
| | 3.THE VENT SYSTEM SHALL TERMINATE AT LEAST 4 FEET |
| | (1219 MM) BELOW, 4 FEET (1219 MM) HORIZONTALLY FROM OR |
| | 1 FOOT |
| | (305 MM) ABOVE ANY DOOR, WINDOW OR GRAVITY AIR INLET |
| | INTO THE BUILDING. |
| | 4.THE VENT TERMINATION POINT SHALL NOT BE LOCATED |
| | CLOSER THAN 3 FEET (914 MM) TO AN INTERIOR CORNER |
| | FORMED BY TWO |
| | WALLS PERPENDICULAR TO EACH OTHER. |
| | 5.THE VENT TERMINATION SHALL NOT BE MOUNTED |
| | DIRECTLY ABOVE OR WITHIN 3 FEET (914 MM) HORIZONTALLY |
| | FROM AN OIL TANK |
| | VENT OR GAS METER. |
| | 6.THE BOTTOM OF THE VENT TERMINATION SHALL BE |
| | LOCATED AT LEAST 12 INCHES (305 MM) ABOVE FINISHED |
| | GRADE. |
| | |
| | 804.3.5 VERTICAL TERMINATIONS. VERTICAL TERMINATIONS |
| | SHALL COMPLY WITH THE FOLLOWING REQUIREMENTS: |
| | 1.WHERE LOCATED ADJACENT TO WALKWAYS, THE |
| | TERMINATION OF MECHANICAL DRAFT SYSTEMS SHALL BE NOT |
| | LESS THAN 7 |
| | FEET (2134 MM) ABOVE THE LEVEL OF THE WALKWAY. |
| | 2.VENTS SHALL TERMINATE AT LEAST 3 FEET (914 MM) |
| | ABOVE ANY FORCED AIR INLET LOCATED WITHIN 10 FEET (3048 |
| | MM). |
| | 3.WHERE THE VENT TERMINATION IS LOCATED BELOW AN |
| | ADJACENT ROOF STRUCTURE, THE TERMINATION POINT SHALL BE |
| | LOCATED AT LEAST 3 FEET (914 MM) FROM |
| | SUCH STRUCTURE. |
| | 4.THE VENT SHALL TERMINATE AT LEAST 4 FEET (1219 |
| | MM) BELOW, 4 FEET (1219 MM) HORIZONTALLY FROM, OR 1 |
| | FOOT (305 MM) ABOVE ANY DOOR, WINDOW OR GRAVITY AIR |
| | INLET FOR THE BUILDING. 5.A VENT CAP SHALL BE |
| | INSTALLED TO PREVENT RAIN FROM ENTERING THE VENT |
| | SYSTEM. |
| | 6.THE VENT TERMINATION SHALL BE LOCATED AT LEAST 3 |
| | FEET (914 MM) HORIZONTALLY FROM ANY PORTION OF THE ROOF |
| | STRUCTURE. |
| | |
| | 501.2 OUTDOOR DISCHARGE. THE AIR REMOVED BY EVERY |
| | MECHANICAL EXHAUST SYSTEM SHALL BE DISCHARGED OUTDOORS |
| | AT A POINT WHERE IT WILL NOT CAUSE A NUISANCE AND FROM |
| | WHICH IT CANNOT AGAIN BE READILY DRAWN IN BY A |
| | VENTILATING SYSTEM. AIR SHALL NOT BE EXHAUSTED INTO AN |
| | ATTIC OR CRAWL SPACE |
| | |
| | 401.5 OPENING LOCATION. |
| | OUTDOOR AIR EXHAUST AND INTAKE OPENINGS SHALL BE |
| | LOCATED A MINIMUM OF 10 FEET (3048 MM) FROM LOT LINES |
| | OR BUILDINGS ON |
| | THE SAME LOT. WHERE OPENINGS FRONT ON A STREET OR |
| | PUBLIC WAY, THE DISTANCE SHALL BE MEASURED TO THE |
| | CENTERLINE OF THE |
| | STREET OR PUBLIC WAY. TING THE LOCATION OF THE |
| | GENERATOR IN RELATIONSHIP TO OTHER STRUCTURES, PLEASE |
| | NOTE IF THERE ARE STRUCTURES WITHIN 10'-0" OF THE |
| | GENERATOR OPENINGS SUCH AS WINDOWS AND DOORS. |
| | ADDITIONAL INFORMATION REQUIRED. POSSIBLE MECHANICAL |
| | ISSUES. |
| | |
| | 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS |
| | OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF |
| | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST |
| | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT |
| | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC |
| | REQUIREMENT, THE SPECIFIC |
| | REQUIREMENT SHALL BE APPLICABLE. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | |
| | |
| | |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |