| 2007-09-17 09:51:15 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | | | | 1.)FLORIDA STATE OR LOCAL PRODUCT APPROVALS REQUIRED | | | IN ADDITION TO THE NOAS SUBMITTED. FAC9B72, | | | WWW.FLORIDABUILDING.ORG | | | | | | 2.)CONFLICTING PAPERWORK WAS SUBMITTED.AN NOA FOR | | | THE TILE UNDERLAYMENT WAS PROVIDED, BUT THIS PROHIBITS | | | DIRECT DECK APPLICATION.A SPEC SHEET STATING THAT THE | | | PRODUCT IS TO BE INSTALLED DIRECT DECK WAS ALSO | | | SUBMITTED.THIS IS NOT ADEQUATE TO SHOW CODE | | | COMPLIANCE.A FLORIDA STATE PRODUCT APPROVAL MAY BE | | | AVAILABLE FOR THE DIRECT DECK APPLICATION, | | | WWW.FLORIDABUILDING.ORG | | | | | | 3.)TWO COMPLETE COLLATED SETS REQUIRED FOR PERMIT | | | ISSUANCE.ONLY ONE GARAGE PLAN WAS SUBMITTED. | | | | | | | | | |
|