2008-02-16 14:09:11** DENIED 2ND REVIEW **
  
 1) NOTE: PLEASE SEE AS NOTED ON PREVIOUS REVIEW. AS
 PLANS HAVE ONLY BEEN SUBMITTED FOR PLAN REVIEW ONLY,
 EVEN ONCE ALL ITEMS ON PLANS ARE OK, REVIEW WILL STILL
 REMAIN IN FAILED STATUS.
 AS PLAN REVIEW, ALL ITEMS EVEN MINOR IN NATURE ARE TO
 BE COMMENTED ON.
  
 2) NOTE: THE RESPONSE LETTER MENTIONS THE GENERATOR IS
 NOW PORTABLE AND THE MANUFACTURES SPECS/CUT SHEET NOW
 INDICATE THIS HOWEVER THE ELECTRICAL PLANS ONLY SHOWS
 *GENERATOR*. THERE IS NO REFERENCE TO THIS UNIT AS
 PORTABLE.
 THE PREVIOUS PLAN REVIEW COMMENT WITH RESPECT TO
 225-31.225.9 AND WHETHER OR NOT THE EXCEPTION IN 702.11
 COULD BE USED. THE RESPONSE MENTIONS 700.12B6 WHICH IS
 FOR EMERGENCY LIFE SAFETY SYSTEMS. PLEASE CLARIFY THIS
 AS THIS OFFICE IS NOT AWARE OF THIS BEING A LEGALLY
 REQUIRED OR LIFE SAFETY GENERATOR FALLING UNDER
 NFPA-110 LEVEL 1 OR LEVEL 2 SYSTEMS.
 IF THERE IS ANY TYPE REQUIREMENT THEN A PERMANENT UNIT
 WOULD BE REQUIRED AND A PORTABLE UNIT WOULD NOT BE
 PERMITTED.
 IF THIS IS INDEED AN OPTIONAL STAND-BY AS 702.1 SCOPE
 SPEAKS OF THEN ONLY SECTIONS OF 702 APPLY.
 PLEASE KNOW UNDER A PORTABLE UNIT AND THE UNIT MEETS
 BOTH EXCEPTIONS AS STATED ON PREVIOUS REVIEW THEN A
 DISCONNECTING MEANS WOULD NOT BE REQUIRED AT BUILDING.
 THIS REVIEW IS NOT REQUIRING AN ITEM WHICH IS ABOVE THE
 MINIMUM CODE.
  
 3) NOTE: SPECIFICATION SHEETS FOR DIVISION SPECS
 REDLINED FOR COLOR CODING FOR ANY 277/480V SYSTEMS TO
 BE BROWN, PURPLE, YELLOW.
  
 ** ONCE REVIEW NOTE #2 IS CLARIFIED, IT DOES NOT APPEAR
 ANY REVISIONS WILL BE NEEDED TO PLANS. COMMENT #1
 REMAINS UNTIL PERMIT IS APPLIED FOR. NEW BUILDING
 CODES, LICENSING ETC WILL BE VERIFIED ONCE PERMIT HAS
 BEEN APPLIED.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved