Plan Review Notes
Plan Review Notes For Permit 07090452
Permit Number 07090452
Review Stop B
Sequence Number 2
Notes
Date Text
2008-04-01 10:05:42****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1A. WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION AND REMOVE AND REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOU
 PERMIT.THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2ND REVIEW, SEE A3, PRESSURES WERE ADDED BUT NOT
 CLOUDED.IT APPEARS THAT POSSIBLY OTHER CHANGES WERE
 MADE TO THE PLANS BUT NOT CLOUDED AND NUMBERED.PLEASE
 CLEARLY INDICATE ALL CHANGES TO THE PLAN TO EXPEDITE
 THE PLAN REVIEW PROCESS.OTHERWISE A COMPLETELY NEW
 REVIEW IS REQUIRED, RATHER THAN CHECKING ONLY THINGS
 WHICH HAVE CHANGED FROM THE PREVIOUS REVIEW.SEE ITEM
 16 AND SHEET S10.FAILURE TO CLOUD ALL CHANGES
 REQUIRES A COMPLETELY NEW REVIEW FOR EACH PAGE, EVERY
 DETAIL, EVERY NOTE.NOTE THAT A COMPLETE REVIEW WAS
 NOT DONE AS CHANGES WERE NOT CLOUDED.PLEASE CLOUD ALL
 CHANGES ON THE PLAN WHICH WERE DONE AFTER THE FIRST
 SUBMITTAL AND THOSE CHANGES WILL BE REVIEWED IN THE
 NEXT REVIEW.
  
 OLD SHEETS WERE NOT SUBMITTED.THIS IS REQUIRED FOR
 REFERENCE.
  
 1B. ADDRESSED.
  
 1C. FBC*106.1.1, DRAWINGS AND SPECIFICATIONS TO BE
 SPECIFIC AND CANNOT REFER TO CODE SECTIONS IN LIEU OF
 DESIGN CRITERIA.
  
 2.THIS REVIEW IS A PLAN REVIEW, OR MAJOR WORKING
 DRAWING REVIEW.THIS PROJECT WILL REMAIN IN FAILED
 STATUS UNTIL APPLICATION FOR PERMIT BY A CONTRACTOR
 LICENSED TO PERFORM OR SUPERVISE THE WORK.IF THE
 PERMIT IS NOT APPLIED FOR PRIOR TO OCTOBER 1, 2008,
 GOVERNING CODE WILL BE FBC2007 RATHER THAN FBC2004 WITH
 2007 REVISIONS/SUPPLEMENTS AS CURRENTLY DESIGNED.
  
 3-8C. ADDRESSED.
  
 8D. ENGINEER STATES THAT THIS IS AN UNOCCUPIED
 BUILDING.SEE FBC1004.1, ALL BUILDINGS ARE TO COMPLY
 WITH EGRESS REQUIREMENTS BASED ON THE GREATER OF EITHER
 DESIGN LOAD (IN THIS CASE, ZERO FOR UNOCCUPIED) OR THE
 OCCUPANT LOAD BASED ON FBC TABLE 1004.1.DESIGNER
 CANNOT DECLARE AN OCCUPANT LOAD LESS THAN REQUIRED IN
 FBC TABLE 1004.1, SEE FBC1004.1. PLEASE DECLARE
 OCCUPANT LOAD.
  
 PLEASE NOTE FBC1001.1, SCOPE; THE BUILDING IS REQUIRED
 TO HAVE AN OCCUPANT LOAD DECLARED BUT THE STORAGE TANK
 WOULD NOT BE CONSIDERED A BUILDING.
  
 8E-G.ADDRESSED.
  
 8H. SQUARE FOOT AREA FOR THE BUILDING WAS PROVIDED.
 PLEASE ALSO PROVIDE SQUARE FOOT AREA FOOTPRINT OF THE
 TANK.
  
 9-11. PRODUCT APPROVALS, ADDRESSED.
  
 12.ENGINEER'S RESPONSE LETTER STATES THAT PRODUCT
 APPROVALS ARE ATTACHED.SEE THE PREVIOUS LIST
 REGARDING INFORMATION REQUIRED FOR ROOF PERMITS.THIS
 INFORMATION MAY BE PROVIDED AT THE TIME OF ROOF PERMIT
 APPLICATION.ROOF DESIGN PRESSURES ON S2 ARE -40.5,
 -67.9, -102.2.
  
 13-14. I WAS ABLE TO LOCATE THE IMPORTANCE FACTOR OF
 1.15 ON S1 BUT THIS WAS NOT CLOUDED.ALL WIND DESIGN
 CRITERIA (INCLUDING IMPORTANCE FACTOR) IS REQUIRED ON
 THE PLANS, FBC1603.ALL CHANGES SHOULD BE CLEARLY
 INDICATED AND THE OLD SHEETS SHOULD BE SUBMITTED FOR
 REFERENCE.
  
 15. ADDRESSED.
  
 16. ENGINEER'S RESPONSE LETTER STATES THAT THE STAIR
 RISER AND TREAD DIMENSIONS HAVE BEEN ADDED TO SHEET
 S10.I WAS ABLE TO LOCATE THE DIMENSIONS BUT PLEASE
 NOTE THAT THIS CHANGE WAS NOT CLOUDED.SEE OTHER
 COMMENTS REGARDING CHANGES TO THE PLAN.
 17-18. ADDRESSED.
  
 19. ENGINEER?S RESPONSE WAS THAT THE TANK MANUFACTURER
 IS RESPONSIBLE FOR THE DESIGN.THIS PERMIT WILL BE
 ISSUED WITH A PROVISO THAT STRUCTURAL INFORMATION BE
 PROVIDED FOR REVIEW PRIOR TO INSTALLATION.
  
 20. ADDRESSED.
  
 NEW COMMENTS:
  
 21.ROOF PLAN A2, NORTH AND EAST ELEVATIONS A3, SHOW
 HANDRAILS.GUARDS ARE TO COMPLY WITH FBC 1012.5 AND
 1607.PLEASE REVISE PLAN TO INCLUDE DESIGN CRITERIA. A
 NOTE ON S9 STATES THAT THE RAIL WILL COMPLY WITH
 "APPLICABLE CODE REQUIREMENTS".SEE COMMENT 1C, DESIGN
 CRITERIA IS TO BE SPECIFIC AND CANNOT REFER TO "CODE"
 EITHER GENERALLY OR BY CODE NUMBER. NEW DETAIL ADDED TO
 PLAN.
  
 22.S10, THE HANDRAIL HEIGHT IS SHOWN GRAPHICALLY AS
 SHORTER THAN THE GUARDRAIL.42INCH MINIMUM IS REQUIRED
 AS THE HANDRAIL ALSO ACTS AS A GUARDRAIL.PLEASE
 CLARIFY (ADD REQUIRED DIMENSION) OR REVISE. SEE
 FBC1009.NEW DETAIL ADDED TO PLAN.
  
 23. CLARIFY S1 DESIGN DATA, N.3.C., EXPOSURE B
 DECLARED.SEE FBC1609.4.3, THIS APPEARS TO BE EXPOSURE
 C.NOTE THAT THE DEFINITION FOR EXPOSURE C CHANGED
 EFFECTIVE DECEMBER 8, 2006.
  
 24.WHEN RESUBMITTING, PLEASE INCLUDE A RESPONSE
 LETTER INDICATING HOW EACH ITEM WAS ADDRESSED.ALSO
 PLEASE CLOUD AND NUMBER ALL CHANGES AND SUBMIT OLD
 SHEETS FOR REFERENCE (FIRST AND SECOND REVIEWS).IT
 APPEARS THAT THIS WAS NOT DONE AS SEVERAL REVISIONS
 WERE NOT CLOUDED BASED ON ENGINEER?S RESPONSE (STATING
 THAT THESE ITEMS WERE ADDED OR REVISED) AND FIRST
 REVIEW.TO EXPEDITE THE PLAN REVIEW PROCESS, ALL
 CHANGES ARE TO BE CLEARLY INDICATED.
  