Plan Review Notes
Plan Review Notes For Permit 07090452
Permit Number 07090452
Review Stop P
Sequence Number 1
Notes
Date Text
2007-10-25 12:57:23DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. PLEASE INDICATE THE OCCUPANCY GROUP & THE SQUARE
 FOOTAGE OF THE BUILDING. SECTIONS 106.1.2, 106.3.5.1(2)
 & 302.1.
  
 2. THE CERTIFICATE OF AUTHORIZTION NUMBER IS REQUIRED
 ON ALL SHEETS WITH THE WORCESTER ENGINEERING INC. TITLE
 BLOCK ON IT. FAC 61G15-23.002(2) & FS 471.025.
  
 3. PER TABLE 403.1 A DRINKING FOUNTAIN AND A SERVICE
 SINK ARE REQUIRED. PLEASE INDICATE THE LOCATION OF EACH
 ON THE FLOOR PLAN.
  
 4. SUBMIT A DETAIL/ELEVATION SHOWING COMPLIANCE WITH
 THE FOLLOWING:
 ___FOR THE W/C:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.3 HEIGHT
 C. 11-4.16.4 GRAB BARS
 D. 11-4.16.5 FLUSH CONTROLS
 E. 11-4.16.6 DISPENSERS
 ___FOR THE LAV:
 A. 11-4.19.2 HEIGHT & CLEARANCES
 B. 11-4.19.3 CLEAR FLOOR SPACE
 C. 11-4.19.4 EXPOSED PIPES & SURFACES
 D. 11-4.19.5 FAUCETS
 E. 11-4.19 6 MIRRORS
 ___FOR THE TOILET ROOM:
 A. 11-4.22.3 TURNING CIRCLE
 ___FOR THE DRINKING FOUNTAIN:
 A. 11-4.15.2 SPOUT HEIGHT
 B. 11-4.15.3 CLEARANCES & CLEAR FLOOR SPACE & SECTION
 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING, (IF NOT A HIGH/LOW
 D/F).
  
 5. SHTS A-2 & A-3. SUBMIT CALCULATIONS FOR THE ROOF
 DRAINAGE PER SECTION 1106 & TABLES 1106.3 & 1106.6.
 INDICATE THE SQUARE FOOTAGE OF THE ROOF AND INDICATE
 1/2 AREA OF ALL VERTICAL WALLS INCLUDING PARAPETS. SHOW
 THE SIZE OF THE GUTTERS AND SHOW THE SIZE OF THE
 DOWNSPOUTS. INDICATE THE SLOPE OF THE GUTTER AND SHOW
 THE HIGH POINTS OF THE GUTTER PER TABLE 1106.6.
  
 6. SHT A-5. PER SECTION 1210.2 THE WALLS WITHIN 2FT OF
 THE WATER CLOSET SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT SURFACE. PLEASE INDICATE HOW PAINT WILL BE
 A NONABSORBENT SURFACE.
  
 7. SHTS M-3 & M-10 SHOWS 3 FLOOR DRAINS, A HOSE REEL,
 AN EXTERIOR HOSE VALVE AND AN EMERGENCY SHOWER/EYE WASH
 NOT INDICATED ON SHT BS-3. PLEASE CORRELATE PLUMBING
 INFORMATION AND SHOW ON THE PLUMBING SHEET. SECTION
 106.1.1.--NO VENTING IS SHOWN FOR THE FLOOR DRAINS
 AS REQUIRED IN SECTION 901.2.1.--THE RISER DIAGRAMS
 SHALL REFLECT ALL PIPING FOR THE SANITARY AND WATER. --
 PLEASE SHOW THE HOSE REEL, THE EXTERIOR HOSE VALVE AND
 EMERGENCY SHOWER/EYE WASH ON THE FLOOR PLANS. SECTION
 106.1.1
  
 8. SHT M-3SHOWS PVC PIPE FOR THE DISTRIBUTION WATER
 TO THE TOILET ROOM.DISTRIBUTION PIPING SHALL COMPLY
 WITH TABLE 605.4. ALSO SEE PLUMBING NOTE #10 ON SHT
 BS-3. PLEASE CORRELATE PIPING INFORMATION.
  
 9. SHTS BS-1, BS-2 & BS-3 THE ADDRESS FOR KAM
 CONSULTING DOES NOT REFLECT THE ADDRESS OF RECORD ON
 THE STATE OF FLORIDA DBPR WEBSITE. (SEE ATTACHED
 SHEET). PLEASE UPDATE THE TITLE BLOCKS OR THE DBPR
 WEBSITE PRIOR TO RESUBMITTING FOR REVIEW. FAC
 61G15-23.002(2) & FS 471.025.
  
 10. SHT BS-3 WATER RISER DIAGRAM. THE WATER HAMMERS
 SHALL BE LOCATED NEAR THE FIXTURES IN AN "EFFECTIVE
 RANGE" NOT IN THE CEILING AS SHOWN. PDI-WH 201, MANUF.
 INSTALLATION INSTRUCTIONS & SEE PLUMBING NOTE 13 THIS
 SHEET.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  