Plan Review Notes
Plan Review Notes For Permit 07090452
Permit Number 07090452
Review Stop M
Sequence Number 1
Notes
Date Text
2007-10-19 15:24:32REVIEW #: 1
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS FBC
 CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PG M-5 SHOWS AN ELECTRIC GENERATOR WITH SUB BASE AND
 SECONDARY FUEL STORAGE TANKS. PROVIDE LISTING,
 SUBMITTALS AND INSTALLATION INSTRUCTIONS FOR THE
 GENERATOR AND FUEL TANKS. WHAT TYPE OF FUEL IS TO BE
 USED? NFPA 37-02 AND FBC 106.1.2
  
 2. ABOVE GROUND FUEL STORAGE TANKS GREATER THAN 550
 GALLONS REQUIRE APPROVAL BY THE PALM BEACH COUNTY DEPT.
 OF ENVIRONMENTAL RESOURCE MANAGEMENT IN ACCORDANCE WITH
 F.S. 376.303. PROVIDE TWO SETS OF PLANS WITH PBC DERM
 APPROVAL FOR PROPOSED FUEL STORAGE SYSTEMS. FOR MORE
 INFORMATION PLEASE CONTACT PBC DERM AT
 WWW.CO.PALM-BEACH.FL.US/ERM/CONTACT.ASP OR
 561-233-2400.
  
 3. SHOW GENERATOR TO BE IN COMPLIANCE WITH NFPA 37-02
 IN ACCORDANCE WITH FBC,M 915.1 AND FUEL STORAGE TANKS
 TO BE IN COMPLIANCE WITH NFPA 30-00 IN ACCORDANCE WITH
 NFPA37-02 SEC. 6.3.3. PLANS CAN NOT BE REVIEWED BY
 THESE STANDARDS AT THIS TIME DUE TO INSUFFICIENT DETAIL
 AND INFORMATION. SEE COMMENT #1. ADDITIONAL COMMENTS
 ARE POSSIBLE ONCE ALL REQUIRED INFORMATION IS
 PROVIDED.
  
 4. SHOW SIZE AND TYPE OF MATERIAL OF FUEL PIPING ALONG
 WITH SUBMITTAL AND INSTALLATION INSTRUCTIONS FOR FUEL
 TRANSFER PUMP TO SHOW COMPLIANCE WITH THE ABOVE STATED
 CODES. FBC 106.1.2
  
 5. PG A-5: EXTERIOR WALL LOUVERS ARE SUBJECT TO FAC
 RULE 9B-72 AND AS SUCH ARE REQUIRED TO HAVE PRODUCT
 APPROVAL. PROVIDE PRODUCT APPROVAL DOCUMENTATION FOR
 ALL EXTERIOR WALL LOUVERS. FOR MORE INFORMATION ON THE
 FLORIDA PRODUCT APPROVAL SYSTEM PLEASE VISIT:
 WWW.FLORIDABUILDING.ORG
  
 6. PG A-2: EF-1 ON ROOF APPEARS TO BE WITHIN 10 FEET OF
 THE ROOF EDGE. GUARDS SHALL BE PROVIDED WHERE
 APPLIANCES, EQUIPMENT, FANS OR OTHER COMPONENTS THAT
 REQUIRE SERVICE ARE LOCATED WITHIN 10 FEET OF A ROOF
 EDGE AND SUCH EDGE OR OPEN SIDE IS LOCATED MORE THAN 30
 INCHESABOVE THE FLOOR OR GRADE BELOW. THE GUARD SHALL
 EXTEND NOT LESS THAN 30 INCHES BEYOND EACH END OF SUCH
 APPLIANCE, EQUIPMENT, FAN OR COMPONENT AND THE TOP OF
 THE GUARD SHALL BE LOCATED NOT LESS THAN 42 INCHES
 ABOVE THE ELEVATED SURFACE ADJACENT TO THE GUARD. THE
 GUARD SHALL BE CONSTRUCTED SO AS TO PREVENT THE PASSAGE
 OF A 21-INCH-DIAMETER SPHERE AND SHALL COMPLY WITH THE
 LOADING REQUIREMENTS FOR GUARDS SPECIFIED IN THE
 FLORIDA BUILDING CODE, BUILDING.FBC,M 304.10.
  
 7. ON PG A-2 EF-1 IS SHOWN OVER THE CHLORINE ROOM, BUT
 ON PG BS-2 EF-1 IS SHOWN IN THE TOILET ROOM. PLEASE
 COORDINATE EQUIPMENT SCHEDULES AND PLANS, UNIQUELY
 IDENTIFYING EACH PIECE OF EQUIPMENT. FBC,M 304.11
  
 8. PG M-10: ROOF EXHAUST FAN DETAIL #121, THERE IS NO
 DETAIL OR SUBMITTAL DATA SHOWING ROOFTOP EXHAUST FANS
 AND SUPPORTS DESIGNED TO MEET WIND LOAD REQUIREMENTS.
 PROVIDE DETAILS AND DATA SHOWING FANS, CURBS AND ALL
 RELATED ATTACHMENTS ARE DESIGNED FOR THIS WIND ZONE
 (140 MPH) IN ACCORDANCE WITH FBC,M 301.13 AND FBC
 CH.16. NOTE: THIS FACILITY WILL BE CONSIDERED TO HAVE A
 WIND IMPORTANCE FACTOROF 1.15 IN ACCORDANCE WITH FBC
 TABLE 1604.5.
  
 9. PG BS-1: HVAC UNIT DETAIL SHOWS AHU-1 BEING FED BY
 CHILLED WATER PIPES, BUT THE EQUIPMENT SCHEDULE AND
 FLOOR PLAN ON BS-2 SHOW A SPLIT SYSTEM WITH REFRIGERANT
 LINES. WHICH IS CORRECT? EQUIPMENT SHALL BE ACCURATELT
 IDENTIFIED ON PLANS IN ACCORDANCE WITH FBC
 106.3.5.1.4.
  
 10. PG BS-1 SHOWS REFRIGERANT LINES ABOVE GROUND AND
 BS-2 SHOWS REFRIGERANT LINES UNDERGROUND. IF
 REFRIGERANT LINES ARE UNDER ANY PORTION OF THE SLAB,
 THEY SHALL BE ENCASED IN A SLEEVE OR PIPE DUCT IN
 ACCORDANCE WITH FBC,M 1107.2.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]