| Date |
Text |
| 2007-10-23 10:54:43 | 1. A KNOX-BOX WILL BE REQUIRED TO ALLOW FOR FIRE AND |
| | PARAMEDICAL ACCESS THRU THE SWING GATES. |
| | |
| | 2. SUITABLE ACCESS SHALL BE PROVIDED FOR FIRE AND |
| | PARAMEDICAL EQUIPMENT TO THE SITE AND APPURTENANT |
| | EQUIPMENT. |
| | |
| | 3. PORTABLE FIRE EXTINGUISHERS DISPLAYED ON THE PLANS |
| | SHALL BE CURRENTLY SERVICE TAGGED BY A LICENSED FIRE |
| | EQUIPMENT COMPANY. |
| | |
| | 4. A SIGN SHALL BE AFFIXED TO DIRECT PERSONS TO THE |
| | APPLICABLE LOCATION AND PROPOSED ADDRESS TO AID IN |
| | EMERGENCY RESPONSE. |
| | |
| | 5. PLEASE PROVIDE PRODUCT APPROVALS AND APPROPRIATE |
| | LISTINGS FOR THE FUEL TANK. TANK WILL MOST LIKELY HAVE |
| | TO BE REGISTERED WITH PBC DERM BASED ON ITS SIZE. |
| | |
| | 6. PLEASE PROVIDE ALL PRODUCT LABELS AND WARNINGS SIGNS |
| | THAT WILL BE PROVIDED FOR THE FUEL TANK. |
| | |
| | 7. PLEASE PROVIDE ALL DETAILS REGARDING VENTING OF THE |
| | FUEL TANK. |
| | |
| | 8. ALL ELECTRICAL INSTALLATIONS TO COMPLY WITH NFPA 70, |
| | THE NATIONAL ELECTICAL CODE. |
| | |
| | 9. ALL CHEMICALS SHALL BE STORED, USED, AND HANDLED IN |
| | ACOCRDANCE WITH NATIONAL, STATE, COUNTY, AND LOCAL |
| | REQUIREMENTS. |
| | |
| | 10. PROPOSED FIRE HYDRANT TO MEET UTILITY AND FIRE |
| | RESCUE STANDARDS. |
| | |
| | 11. THE ACTIVATION OF ANY DUCT SMOKE DETECTORS SHALL |
| | CAUSE THE AIR CONDITIONING UNIT TO SHUT DOWN. |
| | |
| | 12. ALL HANDRAILS AND GUARDRAILS SHALL COMPLY WITH THE |
| | APPLICABLE CODE REQUIREMENTS REGARDING PRESCRIPTIVE |
| | STRENGTH REQUIREMENTS. |
| | |
| | 13. APPROPRIATE WARNING SIGNS AND LABELS SHALL BE |
| | PROVIDED FOR CHEMICAL STORAGE VESSELS AND EQUIPMENT. |
| | |
| | 14. HOW WILL EMERGENCIES BE REPORTED AT THE SITE DURING |
| | OCCUPIED AND UNOCCUPIED TIMES. |
| | |
| | |
| | MIKE CARSILLO, BATTALION CHIEF |
| | 804-4709 PHONE |
| | 804-4774 FAX |