Plan Review Notes
Plan Review Notes For Permit 07090452
Permit Number 07090452
Review Stop E
Sequence Number 1
Notes
Date Text
2007-10-11 11:42:36** DENIED **
  
 1) NOTE: PLEASE KNOW THAT PLANS HAVE ONLY BEEN
 SUBMITTED FOR *PLAN REVIEW* AND HAVE NOT BEEN SUBMITTED
 UNDER PERMIT APPLICATION. WHEN ALL COMMENTS HAVE BEEN
 ADDRESSED AND PERMIT APPLICATION HAS NOT BEEN MADE,
 PLANS WILL STILL REMAIN IN *FAILED* STATUS.
 THERE ARE SEVERAL ITEMS CONFIRMED ONCE APPLICATION HAS
 BEEN MADE.
 **THIS IS FOR INFORMATIONAL PURPOSES ONLY.
  
 2) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
 2002 NFPA-110
  
 ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED
 FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS
 NOT MADE BY OTHER TRADE(S).
  
 3) NOTE: PLEASE CLARIFY THE MEANS OF DISCONNECT
 REQUIRED FOR FEEDERS FROM GENERATOR ON THE LOAD SIDE OR
 LINE SIDE OF THE ATS TO MEET 225.31-225.39.
 BASED ON THE SYMBOLS SHOWN ON THE DP CAN NOT COORDINATE
 THESE WITH THE SYMBOLS ON E-1 SO CAN NOT CONFIRM THIS.
  
 4) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE GENERATOR, ATS AND FUEL TANK. PLEASE
 KNOW THE FUEL TANK WILL BE REVIEWED BY OTHER TRADES
 110.3, 90.7.
 FBC 106.1.2
  
 5) NOTE: PLEASE CLARIFY THE *FUTURE-LOAD* BEING SHOWN
 ON THE GENERATOR WHICH SHOWS THE LOAD EXCEEDING THE
 RATING OF THE UNIT.
 702.5, 220.
 THIS FUTURE SCOPE OF WORK IS NOT BEING SHOWN HOWEVER
 PLEASE BE AWARE THAT THE RATING OF THE GENERATOR IS
 REQUIRED TO RATED FOR THE LOADS BEING SERVED UNLESS
 LOAD SHEDDING DEVICES/EQUIPMENT IS GOING TO BE
 INSTALLED.
 FBC 10
  
 6) NOTE: PLEASE KNOW THAT THE LOW VOLTAGE AS SHOWN ON
 PLANS WILL BE REQUIRED TO BE UNDER SEPARATE PERMITS.
 THE BASE PLANS MAY BE REFERENCED FOR TURN AROUND
 PERMITS.
 THIS IS FOR INFORMATION ONLY.
  
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
2007-10-07 14:19:402007-1007 14:19:40
  
 IN ELECTRIC FOR REVIEW.