| 2007-10-11 11:42:36 | ** DENIED ** |
| | |
| | 1) NOTE: PLEASE KNOW THAT PLANS HAVE ONLY BEEN |
| | SUBMITTED FOR *PLAN REVIEW* AND HAVE NOT BEEN SUBMITTED |
| | UNDER PERMIT APPLICATION. WHEN ALL COMMENTS HAVE BEEN |
| | ADDRESSED AND PERMIT APPLICATION HAS NOT BEEN MADE, |
| | PLANS WILL STILL REMAIN IN *FAILED* STATUS. |
| | THERE ARE SEVERAL ITEMS CONFIRMED ONCE APPLICATION HAS |
| | BEEN MADE. |
| | **THIS IS FOR INFORMATIONAL PURPOSES ONLY. |
| | |
| | 2) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH |
| | ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS |
| | UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | 2002 NFPA-110 |
| | |
| | ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED |
| | FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS |
| | NOT MADE BY OTHER TRADE(S). |
| | |
| | 3) NOTE: PLEASE CLARIFY THE MEANS OF DISCONNECT |
| | REQUIRED FOR FEEDERS FROM GENERATOR ON THE LOAD SIDE OR |
| | LINE SIDE OF THE ATS TO MEET 225.31-225.39. |
| | BASED ON THE SYMBOLS SHOWN ON THE DP CAN NOT COORDINATE |
| | THESE WITH THE SYMBOLS ON E-1 SO CAN NOT CONFIRM THIS. |
| | |
| | 4) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT |
| | SHEETS FOR THE GENERATOR, ATS AND FUEL TANK. PLEASE |
| | KNOW THE FUEL TANK WILL BE REVIEWED BY OTHER TRADES |
| | 110.3, 90.7. |
| | FBC 106.1.2 |
| | |
| | 5) NOTE: PLEASE CLARIFY THE *FUTURE-LOAD* BEING SHOWN |
| | ON THE GENERATOR WHICH SHOWS THE LOAD EXCEEDING THE |
| | RATING OF THE UNIT. |
| | 702.5, 220. |
| | THIS FUTURE SCOPE OF WORK IS NOT BEING SHOWN HOWEVER |
| | PLEASE BE AWARE THAT THE RATING OF THE GENERATOR IS |
| | REQUIRED TO RATED FOR THE LOADS BEING SERVED UNLESS |
| | LOAD SHEDDING DEVICES/EQUIPMENT IS GOING TO BE |
| | INSTALLED. |
| | FBC 10 |
| | |
| | 6) NOTE: PLEASE KNOW THAT THE LOW VOLTAGE AS SHOWN ON |
| | PLANS WILL BE REQUIRED TO BE UNDER SEPARATE PERMITS. |
| | THE BASE PLANS MAY BE REFERENCED FOR TURN AROUND |
| | PERMITS. |
| | THIS IS FOR INFORMATION ONLY. |
| | |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| 2007-10-07 14:19:40 | 2007-1007 14:19:40 |
| | |
| | IN ELECTRIC FOR REVIEW. |