Plan Review Notes
Plan Review Notes For Permit 07090452
Permit Number 07090452
Review Stop B
Sequence Number 1
Notes
Date Text
2007-10-22 16:52:316800 ROEBUCK RD
 WAST WATER TREATMENT PLANT
 REPUMP STATION & 3MG PRE-STRESSED CONCRETE STORAGE
 TANK
 OCT.22/ 2007
  
  
 BUILDING PLAN REVIEW
 PERMIT: 07090452
 ADD: 6800 ROEBUCK RD
 CONT: GLOBALTECH**PLAN
 REVIEW**
 TEL: (954)818-5205
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT.
 IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF
 YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A
 THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID
 DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1*
 /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 2)THIS REVIEW IS BEING DONE AS A PLAN REVIEW OR MAJOR
 WORKING DRAWING REVIEW, PLANS SUBMITTED FOR PERMIT
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE2007 REVISIONS.
  
 3) GLOBALTECH, INC IS MISSING THEIR CERTIFICATE OF
 AUTHORIZATION NUMBER ON THE PLANS.471.023 F.S.
 CERTIFICATE OF AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ENGINEER
 PRACTICING UNDER A FICTITIOUS NAME, A CORPORATION, OR A
 PARTNERSHIP, OFFERING ENGINEERING SERVICES, SHALL
 INCLUDE THE CERTIFICATE OF AUTHORIZATION NUMBER. ADD
 THE NUMBER TO EACH SHEET.THIS MAY
 BE ADDED BY HAND.
  
 4)WORCESTER ENGINEERING, INC. IS MISSING THEIR
 CERTIFICATE OF AUTHORIZATION.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY SHEET BEARING
 THE NAME OF AN ENGINEER
 PRACTICING UNDER A FICTITIOUS NAME, A CORPORATION, OR A
 PARTNERSHIP, OFFERING ENGINEERING SERVICES, SHALL
 INCLUDE THE CERTIFICATE OF AUTHORIZATION NUMBER. ADD
 THE NUMBER TO EACH SHEET.THIS MAY
 BE ADDED BY HAND.
  
 5)HILLERS ELECTRICAL ENGINEERING, INC. IS MISSING
 THEIR CERTIFICATE OF AUTHORIZATION NUMBER. CERTIFICATE
 OF AUTHORIZATION.THE TITLE BLOCK FOR ANY SHEET
 BEARING THE NAME OF AN ENGINEER
 PRACTICING UNDER A FICTITIOUS NAME, A CORPORATION, OR A
 PARTNERSHIP, OFFERING ENGINEERING SERVICES, SHALL
 INCLUDE THE CERTIFICATE OF AUTHORIZATION NUMBER. ADD
 THE NUMBER TO EACH SHEET.THIS MAY
 BE ADDED BY HAND.
  
 6)PROVIDE (3) ORIGINAL SOILS REPORTS THAT WERE
 PREPARED BY DUNKLEBURGER ENGINEERING & TESTING, PROJECT
 NO. 05-21-6014, ORIGINAL SIGNATURE AND SEALED. FBC
 1802.2.1 QUESTIONABLE SOIL.
 WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN
 DOUBT, OR WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT
 SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL REQUIRE THAT THE NECESSARY INVESTIGATION
 BE MADE. SUCH INVESTIGATION SHALL COMPLY WITH THE
 PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 .
  
 7) ALSO, PLEASE ARRANGE WITH HAROLD PISKURA (INSPECTION
 SERVICES MANAGER - TEL: 561 805 6711), A MEETING
 INVOLVING THE OWNER, SPECIALINSPECTOR, JOB INSPECTOR,
 CONTRACTOR AND ENGINEER.
  
 8 ) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE
 OF OCCUPANCY:
 A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT
 IS DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 5,
 TABLE 503.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM ISPROVIDED
 F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE
 BUILDING PERMIT
 H ) SQ. FT. FOOTPRINT
  
 9)PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72.
  
 10) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 11) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR)
 OF PRODUCT TESTING REPORTS ,MISSING REPORTS ARE AS
 FOLLOWS:
 10A) EXTERIOR HOLLOW METAL DOORS, SINGLE AND PAIRS
 10B) WALL LOUVERS
 10C) OVERHEAD METAL COIL DOOR
 10D) ROOFING ASSEMBLIES, FLAT ROOF
  
 12)) THIS ROOF IS MISSING OR NOT IN COMPLIANCE WITH
 THE FOLLOW ITEMS:
 _XX__ CONTRACTOR DID NOT PROVIDE THE MEAN ROOF HEIGHT.
 _XX__ CONTRACTOR FAILED TO INDICATE WHICH SUB-SYSTEM TO
 BE USED.
 _XX__ THE SYSTEM PROVIDED HAS A LOW PRESSURE FOR ZONE
 _2&3__ .
 _XX_ THE SYSTEM PROVIDED STATES LIMITATION# 7, SHOULD
 THE FASTENER RESISTANCE BE LESS THAN THAT EQUIRED, AS
 DETERMINED BY THE BUILDING OFFICIAL, A REVISED FASTENER
 SPACING, PREPARED , SIGNED
 AND SEALED BY A FLORIDA REGISTERED PROFESSIONAL
 ENGINEER, REGISTEREDARCHITECT OR REGISTERED ROOF
 CONSULTANT MAY BE SUBMITTED.
 __XX_CHECK THE SUBMITTAL THE SUB-SYSTEM CHOSEN MAY
 INDICATE LIMITATION# 9, NO ENHANCED FASTENING ALLOWED.
  
 13)PLANS DO NOT PROVIDE THE POSITIVE & NEGATIVE
 PRESSURES FOR DOORS AND WINDOWS NOTE IMPORTANCE FACTOR
 OF 1.15 FOR THE 150 MPH WIND ZONE. ALSO INDICATE END
 ZONES AND INTERIOR ZONES.
 COMPONENTS AND CLADDING 1609.6.1.2.
  
 14) THE PLANS DO NOT PROVIDE THE PRESSURES FOR THE ROOF
 IN ZONES 1,2 OR 3 PLEASE PROVIDE THE POSITIVE AND
 NEGATIVE PRESSURES FOR THE ROOF ZONES. 1609.6.1.2.
  
 15) SHEETS-10 INDICATES A GENERATOR PAD BUT NO
 INFORMATION ON THE ANCHORING OF THE GENERATOR TO THE
 SLAB PLEASE PROVIDETHE QUANTITY OF ANCHORS, SIZE,
 SPACING OF ANCHORS.
 1609.1.3 ANCHORAGE AGAINST OVERTURNING, UPLIFT &
 SLIDING.
  
 16) SHEET S-10 DOES NOT INDICATE THE RIS OR RUN FOR THE
 STAIRS SHOWN ON THIS SHEET, PLEASE PROVIDE COMPLIANCE
 WITH 1009.3.
  
 17) AT THIS TIME THERE IS NO INFORMATION SUPPLIED FOR
 THE GENERATOR, FUEL STORAGE VAULT, PLEASE SUPPLY CUT
 SHEETS ADDITIONAL COMMENTS MAY APPEAR ONCE THESE
 DOCUMENTS HAVE BEEN EXAMINED.
 106.1.2, ADDITIONAL INFORMATION REQUIRED,
  
 18)NOTE: OUTDOOR STORAGE, DISPENSING AND USE. THE
 OUTDOOR STORAGE, DISPENSING AND USE OF HAZARDOUS
 MATERIALS SHALL BE IN ACCORDANCE WITH THE FLORIDA FIRE
 PREVENTION CODE.
  
 19)PLEASE PROVIDE ADDITIONAL INFORMATION FOR THE 3 MG
 PRE-STRESSED CONCRETE STORAGE TANK, THERE ARE NO PLANS
 FOR THIS PORTION OF WORK.106.1.2 ADDITIONAL INFORMATION
 REQUIRED.
 106.3.5 MINIMUM CRITERIA FOR PLAN REVIEW.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  
  
  