| 2007-10-22 16:52:31 | 6800 ROEBUCK RD |
| | WAST WATER TREATMENT PLANT |
| | REPUMP STATION & 3MG PRE-STRESSED CONCRETE STORAGE |
| | TANK |
| | OCT.22/ 2007 |
| | |
| | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 07090452 |
| | ADD: 6800 ROEBUCK RD |
| | CONT: GLOBALTECH**PLAN |
| | REVIEW** |
| | TEL: (954)818-5205 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1A)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS, |
| | REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR |
| | REVIEW FOR PERMIT. |
| | IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF |
| | YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A |
| | THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID |
| | DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1* |
| | /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH |
| | ADMINISTRATIVE CODE. |
| | |
| | 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 |
| | DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN |
| | THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF |
| | MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY |
| | WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE |
| | SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS |
| | A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS |
| | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 2)THIS REVIEW IS BEING DONE AS A PLAN REVIEW OR MAJOR |
| | WORKING DRAWING REVIEW, PLANS SUBMITTED FOR PERMIT |
| | AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| | BUILDING WITH THE2007 REVISIONS. |
| | |
| | 3) GLOBALTECH, INC IS MISSING THEIR CERTIFICATE OF |
| | AUTHORIZATION NUMBER ON THE PLANS.471.023 F.S. |
| | CERTIFICATE OF AUTHORIZATION.THE TITLE BLOCK FOR ANY |
| | SHEET BEARING THE NAME OF AN ENGINEER |
| | PRACTICING UNDER A FICTITIOUS NAME, A CORPORATION, OR A |
| | PARTNERSHIP, OFFERING ENGINEERING SERVICES, SHALL |
| | INCLUDE THE CERTIFICATE OF AUTHORIZATION NUMBER. ADD |
| | THE NUMBER TO EACH SHEET.THIS MAY |
| | BE ADDED BY HAND. |
| | |
| | 4)WORCESTER ENGINEERING, INC. IS MISSING THEIR |
| | CERTIFICATE OF AUTHORIZATION.CERTIFICATE OF |
| | AUTHORIZATION.THE TITLE BLOCK FOR ANY SHEET BEARING |
| | THE NAME OF AN ENGINEER |
| | PRACTICING UNDER A FICTITIOUS NAME, A CORPORATION, OR A |
| | PARTNERSHIP, OFFERING ENGINEERING SERVICES, SHALL |
| | INCLUDE THE CERTIFICATE OF AUTHORIZATION NUMBER. ADD |
| | THE NUMBER TO EACH SHEET.THIS MAY |
| | BE ADDED BY HAND. |
| | |
| | 5)HILLERS ELECTRICAL ENGINEERING, INC. IS MISSING |
| | THEIR CERTIFICATE OF AUTHORIZATION NUMBER. CERTIFICATE |
| | OF AUTHORIZATION.THE TITLE BLOCK FOR ANY SHEET |
| | BEARING THE NAME OF AN ENGINEER |
| | PRACTICING UNDER A FICTITIOUS NAME, A CORPORATION, OR A |
| | PARTNERSHIP, OFFERING ENGINEERING SERVICES, SHALL |
| | INCLUDE THE CERTIFICATE OF AUTHORIZATION NUMBER. ADD |
| | THE NUMBER TO EACH SHEET.THIS MAY |
| | BE ADDED BY HAND. |
| | |
| | 6)PROVIDE (3) ORIGINAL SOILS REPORTS THAT WERE |
| | PREPARED BY DUNKLEBURGER ENGINEERING & TESTING, PROJECT |
| | NO. 05-21-6014, ORIGINAL SIGNATURE AND SEALED. FBC |
| | 1802.2.1 QUESTIONABLE SOIL. |
| | WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN |
| | DOUBT, OR WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT |
| | SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING |
| | OFFICIAL SHALL REQUIRE THAT THE NECESSARY INVESTIGATION |
| | BE MADE. SUCH INVESTIGATION SHALL COMPLY WITH THE |
| | PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 . |
| | |
| | 7) ALSO, PLEASE ARRANGE WITH HAROLD PISKURA (INSPECTION |
| | SERVICES MANAGER - TEL: 561 805 6711), A MEETING |
| | INVOLVING THE OWNER, SPECIALINSPECTOR, JOB INSPECTOR, |
| | CONTRACTOR AND ENGINEER. |
| | |
| | 8 ) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION |
| | THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE |
| | OF OCCUPANCY: |
| | A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT |
| | IS DESIGNED. |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE |
| | PROVISIONS OF CHAPTER 3. |
| | C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 5, |
| | TABLE 503. |
| | D) THE OCCUPANT LOAD, SEE 1004. |
| | E) IF AN AUTOMATIC SPRINKLER SYSTEM ISPROVIDED |
| | F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED. |
| | G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE |
| | BUILDING PERMIT |
| | H ) SQ. FT. FOOTPRINT |
| | |
| | 9)PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION |
| | AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE |
| | SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. |
| | PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT |
| | IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT |
| | HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR |
| | LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE |
| | 9B-72. |
| | |
| | 10) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE |
| | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |
| | 11) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, |
| | PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR) |
| | OF PRODUCT TESTING REPORTS ,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | 10A) EXTERIOR HOLLOW METAL DOORS, SINGLE AND PAIRS |
| | 10B) WALL LOUVERS |
| | 10C) OVERHEAD METAL COIL DOOR |
| | 10D) ROOFING ASSEMBLIES, FLAT ROOF |
| | |
| | 12)) THIS ROOF IS MISSING OR NOT IN COMPLIANCE WITH |
| | THE FOLLOW ITEMS: |
| | _XX__ CONTRACTOR DID NOT PROVIDE THE MEAN ROOF HEIGHT. |
| | _XX__ CONTRACTOR FAILED TO INDICATE WHICH SUB-SYSTEM TO |
| | BE USED. |
| | _XX__ THE SYSTEM PROVIDED HAS A LOW PRESSURE FOR ZONE |
| | _2&3__ . |
| | _XX_ THE SYSTEM PROVIDED STATES LIMITATION# 7, SHOULD |
| | THE FASTENER RESISTANCE BE LESS THAN THAT EQUIRED, AS |
| | DETERMINED BY THE BUILDING OFFICIAL, A REVISED FASTENER |
| | SPACING, PREPARED , SIGNED |
| | AND SEALED BY A FLORIDA REGISTERED PROFESSIONAL |
| | ENGINEER, REGISTEREDARCHITECT OR REGISTERED ROOF |
| | CONSULTANT MAY BE SUBMITTED. |
| | __XX_CHECK THE SUBMITTAL THE SUB-SYSTEM CHOSEN MAY |
| | INDICATE LIMITATION# 9, NO ENHANCED FASTENING ALLOWED. |
| | |
| | 13)PLANS DO NOT PROVIDE THE POSITIVE & NEGATIVE |
| | PRESSURES FOR DOORS AND WINDOWS NOTE IMPORTANCE FACTOR |
| | OF 1.15 FOR THE 150 MPH WIND ZONE. ALSO INDICATE END |
| | ZONES AND INTERIOR ZONES. |
| | COMPONENTS AND CLADDING 1609.6.1.2. |
| | |
| | 14) THE PLANS DO NOT PROVIDE THE PRESSURES FOR THE ROOF |
| | IN ZONES 1,2 OR 3 PLEASE PROVIDE THE POSITIVE AND |
| | NEGATIVE PRESSURES FOR THE ROOF ZONES. 1609.6.1.2. |
| | |
| | 15) SHEETS-10 INDICATES A GENERATOR PAD BUT NO |
| | INFORMATION ON THE ANCHORING OF THE GENERATOR TO THE |
| | SLAB PLEASE PROVIDETHE QUANTITY OF ANCHORS, SIZE, |
| | SPACING OF ANCHORS. |
| | 1609.1.3 ANCHORAGE AGAINST OVERTURNING, UPLIFT & |
| | SLIDING. |
| | |
| | 16) SHEET S-10 DOES NOT INDICATE THE RIS OR RUN FOR THE |
| | STAIRS SHOWN ON THIS SHEET, PLEASE PROVIDE COMPLIANCE |
| | WITH 1009.3. |
| | |
| | 17) AT THIS TIME THERE IS NO INFORMATION SUPPLIED FOR |
| | THE GENERATOR, FUEL STORAGE VAULT, PLEASE SUPPLY CUT |
| | SHEETS ADDITIONAL COMMENTS MAY APPEAR ONCE THESE |
| | DOCUMENTS HAVE BEEN EXAMINED. |
| | 106.1.2, ADDITIONAL INFORMATION REQUIRED, |
| | |
| | 18)NOTE: OUTDOOR STORAGE, DISPENSING AND USE. THE |
| | OUTDOOR STORAGE, DISPENSING AND USE OF HAZARDOUS |
| | MATERIALS SHALL BE IN ACCORDANCE WITH THE FLORIDA FIRE |
| | PREVENTION CODE. |
| | |
| | 19)PLEASE PROVIDE ADDITIONAL INFORMATION FOR THE 3 MG |
| | PRE-STRESSED CONCRETE STORAGE TANK, THERE ARE NO PLANS |
| | FOR THIS PORTION OF WORK.106.1.2 ADDITIONAL INFORMATION |
| | REQUIRED. |
| | 106.3.5 MINIMUM CRITERIA FOR PLAN REVIEW. |
| | |
| | 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS |
| | OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF |
| | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST |
| | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT |
| | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC |
| | REQUIREMENT, THE SPECIFIC |
| | REQUIREMENT SHALL BE APPLICABLE. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | |
| | |
| | |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |