 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE CODES REFERENCED IN THE ELECTRICAL NOTES, SHEET
 #1, ARE NOT CURRENT. CHANGE THE NOTES TO INDICATE THE
 CODES THIS PROJECT WAS DESIGNED UNDER. 106.1.3 FBC AS
 AMENDED.* THE CHANGES ON SHEET 4A ARE NOTED BUT SHEET
 #1, NOTE #7,IS STILL INCORRECT.
  
 2} PLEASE PROVIDE A PANEL SCHEDULE SO THAT
 BRANCH/FEEDER CIRCUIT CONDUCTOR AND OVERCURRENT
 PROTECTION COMPLIANCE MAY BE REVIEWED PER 106.3.5.4 FBC
 AS AMENDED. SEE 408.4 2005 NEC. * THE JACCUZZI AND
 WATER HEATER IN THE LOAD CALCULATIONS ARE NOT ON THE
 LOAD CALCULATIONS. CORRELATE SAME.
  
 3} INDICATE IF THE A/C SYSTEM IS NEW OR EXISTING. IF
 NEW LOCATE THE AHU ON THE PLAN.* STILL NOT ON THE
 ELECTRICAL PLAN.
  
 4} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH
 210.52(A), 210.52(C), AND 210.8(A)(6) GFI.* NOT ALL ARE
 INDICATED AS GFI.
  
 5} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. WHEN
 INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE PROVIDED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE ALARMS
 SHALL BE INTERCONNECTED AND HARD WIRED. PLEASE INDICATE
 SAME ON PLANS. *OK, SO NOTED.
  
 6} THE NOTE ON SHEET #4 "FOR REFERENCE ONLY" SEEMS TO
 IMPLY THAT THE ENGINEER THAT SIGNED AND SEALED THIS
 SHEET IS NOT TAKING RESPONSIBILITY FOR THE DESIGN. PER
 106.1.3, 106.3.4.3 FBC AS AMENDED, THE PERSON TAKING
 RESPONSIBILITY MUST COMPLY WITH THE STATUTES. REMOVE
 THE NOTE OR REMOVE THE SEAL AND SIGNATURE AND HAVE THE
 PERSON TAKING RESPONSIBILITY COMPLY. *OK, CONTRACTOR
 MAY PRINT AND SIGN AS DESIGNER PER 471.OO3(H)
 EXEMPTION.
  
 NEW COMMENTS :
  
 7} THE RISER DIAGRAM HAS CHANGED TO A DUPLEX METER WITH
 ONE 125 AMP MAIN BREAKER PANEL. THIS PANEL NEEDS TO BE
 LOCATED ON THE FLOOR PLAN SO THAT COMPLIANCE WITH
 ARTICLE 230.70(A) MAY BE REVIEWED.
  
 8} THE PLAN INDICATES A 200 AMP EXISTING PANEL ON THE
 EXTERIOR OF THE ADDITION. THIS IS OBVIOUSLY RELOCATED,
 NOT EXISTING. THE METER AT THIS SAME LOCATION IS NOT
 SHOWN AS A DUPLEX. CORRELATE THE RISER AND THE DRAWING,
 INDICATE THE AIC RATING OF ALL SERVICE EQUIPMENT NEW OR
 RELOCATED.
  
 9} THE HEAT LOAD IN THE ELECTRICAL CALCULATIONS IS
 LISTED AS 500 VA. SHEET #6 LISTS THAT LOAD AS 9.6KW.
 CORRELATE SAME.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH