| 2007-10-25 08:18:20 | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND |
| | NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | 1} THE CODES REFERENCED IN THE ELECTRICAL NOTES, SHEET |
| | #1, ARE NOT CURRENT. CHANGE THE NOTES TO INDICATE THE |
| | CODES THIS PROJECT WAS DESIGNED UNDER. 106.1.3 FBC AS |
| | AMENDED.* THE CHANGES ON SHEET 4A ARE NOTED BUT SHEET |
| | #1, NOTE #7,IS STILL INCORRECT. |
| | |
| | 2} PLEASE PROVIDE A PANEL SCHEDULE SO THAT |
| | BRANCH/FEEDER CIRCUIT CONDUCTOR AND OVERCURRENT |
| | PROTECTION COMPLIANCE MAY BE REVIEWED PER 106.3.5.4 FBC |
| | AS AMENDED. SEE 408.4 2005 NEC. * THE JACCUZZI AND |
| | WATER HEATER IN THE LOAD CALCULATIONS ARE NOT ON THE |
| | LOAD CALCULATIONS. CORRELATE SAME. |
| | |
| | 3} INDICATE IF THE A/C SYSTEM IS NEW OR EXISTING. IF |
| | NEW LOCATE THE AHU ON THE PLAN.* STILL NOT ON THE |
| | ELECTRICAL PLAN. |
| | |
| | 4} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH |
| | 210.52(A), 210.52(C), AND 210.8(A)(6) GFI.* NOT ALL ARE |
| | INDICATED AS GFI. |
| | |
| | 5} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. WHEN |
| | INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A |
| | PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE |
| | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| | DWELLING UNIT SHALL BE PROVIDED WITH SMOKE ALARMS |
| | LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE ALARMS |
| | SHALL BE INTERCONNECTED AND HARD WIRED. PLEASE INDICATE |
| | SAME ON PLANS. *OK, SO NOTED. |
| | |
| | 6} THE NOTE ON SHEET #4 "FOR REFERENCE ONLY" SEEMS TO |
| | IMPLY THAT THE ENGINEER THAT SIGNED AND SEALED THIS |
| | SHEET IS NOT TAKING RESPONSIBILITY FOR THE DESIGN. PER |
| | 106.1.3, 106.3.4.3 FBC AS AMENDED, THE PERSON TAKING |
| | RESPONSIBILITY MUST COMPLY WITH THE STATUTES. REMOVE |
| | THE NOTE OR REMOVE THE SEAL AND SIGNATURE AND HAVE THE |
| | PERSON TAKING RESPONSIBILITY COMPLY. *OK, CONTRACTOR |
| | MAY PRINT AND SIGN AS DESIGNER PER 471.OO3(H) |
| | EXEMPTION. |
| | |
| | NEW COMMENTS : |
| | |
| | 7} THE RISER DIAGRAM HAS CHANGED TO A DUPLEX METER WITH |
| | ONE 125 AMP MAIN BREAKER PANEL. THIS PANEL NEEDS TO BE |
| | LOCATED ON THE FLOOR PLAN SO THAT COMPLIANCE WITH |
| | ARTICLE 230.70(A) MAY BE REVIEWED. |
| | |
| | 8} THE PLAN INDICATES A 200 AMP EXISTING PANEL ON THE |
| | EXTERIOR OF THE ADDITION. THIS IS OBVIOUSLY RELOCATED, |
| | NOT EXISTING. THE METER AT THIS SAME LOCATION IS NOT |
| | SHOWN AS A DUPLEX. CORRELATE THE RISER AND THE DRAWING, |
| | INDICATE THE AIC RATING OF ALL SERVICE EQUIPMENT NEW OR |
| | RELOCATED. |
| | |
| | 9} THE HEAT LOAD IN THE ELECTRICAL CALCULATIONS IS |
| | LISTED AS 500 VA. SHEET #6 LISTS THAT LOAD AS 9.6KW. |
| | CORRELATE SAME. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |
| | [email protected] |