Plan Review Notes
Plan Review Notes For Permit 07090435
Permit Number 07090435
Review Stop E
Sequence Number 1
Notes
Date Text
2007-09-18 10:50:50 
  
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE CODES REFERENCED IN THE ELECTRICAL NOTES, SHEET
 #1, ARE NOT CURRENT. CHANGE THE NOTES TO INDICATE THE
 CODES THIS PROJECT WAS DESIGNED UNDER. 106.1.3 FBC AS
 AMENDED.
  
 2} PLEASE PROVIDE A PANEL SCHEDULE SO THAT
 BRANCH/FEEDER CIRCUIT CONDUCTOR AND OVERCURRENT
 PROTECTION COMPLIANCE MAY BE REVIEWED PER 106.3.5.4 FBC
 AS AMENDED. SEE 408.4 2005 NEC.
  
 3} INDICATE IF THE A/C SYSTEM IS NEW OR EXISTING. IF
 NEW LOCATE THE AHU ON THE PLAN.
  
 4} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH
 210.52(A), 210.52(C), AND 210.8(A)(6) GFI.
  
 5} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. WHEN
 INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE PROVIDED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE ALARMS
 SHALL BE INTERCONNECTED AND HARD WIRED. PLEASE INDICATE
 SAME ON PLANS.
  
 6} THE NOTE ON SHEET #4 ?FOR REFERENCE ONLY? SEEMS TO
 IMPLY THAT THE ENGINEER THAT SIGNED AND SEALED THIS
 SHEET IS NOT TAKING RESPONSIBILITY FOR THE DESIGN. PER
 106.1.3, 106.3.4.3 FBC AS AMENDED, THE PERSON TAKING
 RESPONSIBILITY MUST COMPLY WITH THE STATUTES. REMOVE
 THE NOTE OR REMOVE THE SEAL AND SIGNATURE AND HAVE THE
 PERSON TAKING RESPONSIBILITY COMPLY.
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]