| | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND |
| | NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | 1} THE CODES REFERENCED IN THE ELECTRICAL NOTES, SHEET |
| | #1, ARE NOT CURRENT. CHANGE THE NOTES TO INDICATE THE |
| | CODES THIS PROJECT WAS DESIGNED UNDER. 106.1.3 FBC AS |
| | AMENDED. |
| | |
| | 2} PLEASE PROVIDE A PANEL SCHEDULE SO THAT |
| | BRANCH/FEEDER CIRCUIT CONDUCTOR AND OVERCURRENT |
| | PROTECTION COMPLIANCE MAY BE REVIEWED PER 106.3.5.4 FBC |
| | AS AMENDED. SEE 408.4 2005 NEC. |
| | |
| | 3} INDICATE IF THE A/C SYSTEM IS NEW OR EXISTING. IF |
| | NEW LOCATE THE AHU ON THE PLAN. |
| | |
| | 4} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH |
| | 210.52(A), 210.52(C), AND 210.8(A)(6) GFI. |
| | |
| | 5} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. WHEN |
| | INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A |
| | PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE |
| | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| | DWELLING UNIT SHALL BE PROVIDED WITH SMOKE ALARMS |
| | LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE ALARMS |
| | SHALL BE INTERCONNECTED AND HARD WIRED. PLEASE INDICATE |
| | SAME ON PLANS. |
| | |
| | 6} THE NOTE ON SHEET #4 ?FOR REFERENCE ONLY? SEEMS TO |
| | IMPLY THAT THE ENGINEER THAT SIGNED AND SEALED THIS |
| | SHEET IS NOT TAKING RESPONSIBILITY FOR THE DESIGN. PER |
| | 106.1.3, 106.3.4.3 FBC AS AMENDED, THE PERSON TAKING |
| | RESPONSIBILITY MUST COMPLY WITH THE STATUTES. REMOVE |
| | THE NOTE OR REMOVE THE SEAL AND SIGNATURE AND HAVE THE |
| | PERSON TAKING RESPONSIBILITY COMPLY. |