| 2007-10-08 15:51:04 | |
| | |
| | DENIED |
| | |
| | 1)PLANS AND SPECIFICATIONS DESIGN PARAMETERS SHALL |
| | COMPLY WITH THE 2004 FLORIDA BLDG CODE WITH 2006 |
| | AMENDMENTS PER 106.1.1 FBC* |
| | |
| | 2)IN AN EXISTING BUILDING WHERE ALTERATIONS ARE BEING |
| | MADE A DESIGN PROFESSIONAL MUST ELECT THE LEVEL OF |
| | ALTERATION PER 301.5 OF EXISTING BUILDING CODE AND |
| | STATE ALONG WITH THE TYPE OF CONSTRUCTION ON THE |
| | DRAWINGS |
| | |
| | 3)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON |
| | SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER |
| | ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE |
| | ADDED TO THE PERMIT APPLICATION FEES |
| | |
| | NOTE: FEES ARE DUE IN THE AMOUNT OF $ FOR STATE |
| | RADON FEES THIS AMOUNT IS REQUIRED TO BE PAID PRIOR TO |
| | FURTHER PLAN REVIEW |
| | |
| | 4)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF |
| | EACH PRODUCT APPROVAL THAT IS RELEVANT PER 9B-72. THESE |
| | SHOULD INCLUDE THE FLORIDA STATE APPROVAL COVER PAGES. |
| | ALL CAN BE FOUND ON WWW.FLORIDABUILDING.ORG |
| | |
| | 5)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE |
| | 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC* |
| | |
| | 6)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA |
| | STATE PRODUCT APPROVAL COVER |
| | SHEETS WHEN AVAILABLE. THEY CAN BE SEARCHED FOR ON |
| | WWW.FLORIDABUILDING.ORG.WHEN AVAILABLE AND NOT |
| | SUBMITTED APPLICATIONS WILL BE DENIED |
| | *****PLEASE SEE TOP OF PRODUCT APPROVALS FOR THE |
| | CORRECT FLORIDA STATEWIDE APPROVAL NUMBERS**** |
| | |
| | 7)NO PRODUCT APPROVALS WERE SUBMITTED FOR CASTCRETE |
| | LINTELS AND CONNECTORS AND STRAPS OR THEY MUST ALL BE |
| | LISTED IN THE SCHEDULE COMPLETE WITH FLORIDA PRODUCT |
| | APPROVAL NUMBERS |
| | |
| | 8)SUBMIT ENERGY CALC'S PER 13-101.2.2 FBC. BE SURE |
| | THAT THEY ARE SIGNED AND DATED BY PREPARER AND |
| | OWNER/AGENT PRIOR TO SUBMITTAL |
| | ***** PLEASE NOTE THAT THE ENERGY CALC'S ARE NOT |
| | MATCHING R-VALUES PROVIDED ON THE PERMIT DRAWINGS |
| | (RAISED FLOOR IS R19 IN PLANS AND R-11 IN THE ENERGY |
| | CALC'S) ALSO CALC'S SHALL BE SIGNED AND DATED BUY |
| | OWNER/AGENT***** |
| | |
| | 9)PROVIDE WINDOW SCHEDULE THAT STATES SIZE (REPLACED |
| | EXISTING) AND TYPE OF WINDOW (FIXED,CASEMENT,ETC) AND |
| | THEIR LOCATION (MARK) |
| | |
| | 10)PROVIDE DETAIL OF CONNECTION FOR 2X4 INFILL RAFTER |
| | TO 2X10 RAFTER AT NEW PEAK AND TO EXISTING ROOF |
| | |
| | 11)NOTE S-3 TYPE CONNECTOR (H10) WILL NEED TO BE |
| | (H10-2) FOR DOUBLE GIRDER APPLICATION OVER TERRACE |
| | AREA |
| | |
| | 12)NOTE THAT MBHA THAT IS SPECIFIED FOR RIDGE |
| | LOCATION AT RIDGE BEAM HAVE A MIN WIDTH OF 3 1/8" |
| | |
| | 13)SHOW AREA TO BE VAULTED, DOES IT BEGIN AT NEW |
| | GIRDER TRUSS? AND WHAT IS THE MAKE UP OF THE GIRDER IS |
| | IT ENGINEERED OR A BUILT UP GIRDER? |
| | |