| 2007-09-20 15:18:25 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC |
| | FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | FROM PREVIOUS LIST: |
| | |
| | 1.)ALL INFORMATION REQUIRED BY FAC61G15-23.002 IS |
| | REQUIRED (CERTIFICATE OF AUTHORIZATION FOR THE |
| | ENGINEERING FIRM). |
| | |
| | 2ND REVIEW - THE RESUB SHEET HAS A STATEMENT ON IT - |
| | "THIS IS PER REVIEWER'S NOTES - NEED SIGNED AND SEALED |
| | ON BOTH PAGES OF ENGINEERING REPORT.THIS IS THE |
| | REVISION SUBMISSION.REVISED ENGINEERING REPORT WITH |
| | BOTH PAGES SIGNED AND SEALED." |
| | |
| | PLEASE NOTE THE FOLLOWING: |
| | |
| | A.THIS IS A SPECIFICATION, NOT A REPORT. |
| | |
| | B.ALTHOUGH THIS WAS NOT MY COMMENT, I AGREE THAT BOTH |
| | SHEETS SHOULD BE SEALED (OR USE AN INDEX SHEET), BUT |
| | ALL INFORMATION REQUIRED BY FAC61G15-23.002 IS TO BE ON |
| | EACH SHEET.NOTE THAT THE SECOND SHEET DOES NOT HAVE A |
| | TITLE BLOCK. |
| | |
| | C.THE ACTUAL COMMENT WAS NOT ADDRESSED - THE |
| | CERTIFICATE OF AUTHORIZATION FOR THE FIRM IS TO BE ON |
| | EACH SHEET. |
| | |
| | NEW COMMENT: |
| | |
| | 2.)THE ENGINEERING STATES THAT FOR PARAPET HEIGHT 3', |
| | ZONES 3 AND 4 CAN BE TREATED AS ZONE 2.ZONE 4 IS A |
| | WALL; ZONE 2 IS A ROOF.PLEASE REVISE OR NOTE WHERE IN |
| | ASCE7 THIS IS STATED. |
| | |