2007-12-18 13:22:03****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.PROVIDE TWO COMPLETE SETS OF PERMIT DOCUMENTS FOR
 PERMIT ISSUANCE (ONLY ONE INSTALLATION SCHEDULE
 PROVIDED).
  
 2. SPECIFY SHUTTER TYPE FOR OPENING 5.
  
 3.OPENING 5, ANCHOR SPACING IS 2".ANCHORS WHICH ARE
 TOO CLOSE CAN COMPROMISE THE SUBSTRATE.EITHER REVISE
 OR PROVIDE ENGINEERING TO SHOW THAT 2" SPACING IS
 ACCEPTABLE.NOTE THAT THE CLOSEST ANCHOR SPACING ON
 THE ANCHOR CHART IS 3".
  
 4.OPENING 7 SHOWS 7W FOR THE BOTTOM, 6.5" ANCHOR
 SPACING.7W IS A CEILING TRUSS CONNECTION, 24"
 SPACING.HOW CAN YOU USE THIS AS THE BOTTOM
 CONNECTION?PLEASE CLARIFY.
  
 5.OPENINGS 8-13, CONNECTION 5 IS FOR A WALL TOP
 CONNECTION, SEE SHEET 13.
  
 6.PLEASE CHECK ALL OTHER OPENINGS FOR ERRORS.
  
 7.THERE IS ANOTHER APPLICATION PENDING FOR THE SAME
 SCOPE OF WORK, 07060867.PLEASE ADDRESS.
  