| Plan Review Notes For Permit 07090406 |
| Permit Number |
07090406 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-12-18 13:22:03 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.PROVIDE TWO COMPLETE SETS OF PERMIT DOCUMENTS FOR | | | PERMIT ISSUANCE (ONLY ONE INSTALLATION SCHEDULE | | | PROVIDED). | | | | | | 2. SPECIFY SHUTTER TYPE FOR OPENING 5. | | | | | | 3.OPENING 5, ANCHOR SPACING IS 2".ANCHORS WHICH ARE | | | TOO CLOSE CAN COMPROMISE THE SUBSTRATE.EITHER REVISE | | | OR PROVIDE ENGINEERING TO SHOW THAT 2" SPACING IS | | | ACCEPTABLE.NOTE THAT THE CLOSEST ANCHOR SPACING ON | | | THE ANCHOR CHART IS 3". | | | | | | 4.OPENING 7 SHOWS 7W FOR THE BOTTOM, 6.5" ANCHOR | | | SPACING.7W IS A CEILING TRUSS CONNECTION, 24" | | | SPACING.HOW CAN YOU USE THIS AS THE BOTTOM | | | CONNECTION?PLEASE CLARIFY. | | | | | | 5.OPENINGS 8-13, CONNECTION 5 IS FOR A WALL TOP | | | CONNECTION, SEE SHEET 13. | | | | | | 6.PLEASE CHECK ALL OTHER OPENINGS FOR ERRORS. | | | | | | 7.THERE IS ANOTHER APPLICATION PENDING FOR THE SAME | | | SCOPE OF WORK, 07060867.PLEASE ADDRESS. | | | |
|