Plan Review Notes
Plan Review Notes For Permit 07090403
Permit Number 07090403
Review Stop E
Sequence Number 2
Notes
Date Text
2007-12-03 16:13:50 
  
 ** DENIED REVIEW **
  
 ** PLEASE SEE THERE ARE NOTES FROM PREVIOUS REVIEW
 WHICH ARE STILL IN NEED OF ADDRESSING ALONG WITH NEW
 NOTES.
  
  
  
 1) NOTE:PLEASE SEE THE MANUFACTURES SPECS/CUT SHEETS
 HAVE NOT BEEN SUBMITTED FOR EQUIPMENT INCLUDING
 TRANSFER SWITCH(S) AS REQUESTED ON PREVIOUS REVIEW.
 AS EACH SITE IS *SITE SPECIFIC* EACH SET OF PLANS AND
 RECORD DOCUMENTS ARE REQUIRED TO BE SITE SPECIFIC TO
 EACH LOCATION.
 110.3, 90.7
 FBC 106.1.2
  
 2) NOTE: PLEASE SEE FS 365.172. PLEASE PROVIDE
 DOCUMENTATION AS TO WHETHER OR NOT THE BACK UP SYSTEM
 IS PART OF A E-911 SYSTEM.
 PLEASE SEE NFPA-1221 CHAPTER 4 AS THIS WOULD REQUIRE
 BACK UP POWER FOR ANY LEGALLY REQUIRED SYSTEM.
 IF THE BACK UP SYSTEM IS REQUIRED BY LAW PLEASE PROVIDE
 DOCUMENTS AND PLANS ACCORDINGLY.
 PLEASE ALSO SEE TITLE 47 OF THE FEDERAL US CODE.
 THIS IS A NEW NOTE AND CLARIFICATION OF SYSTEM IS
 NEEDED.
  
 3) NOTE: PLEASE PROVIDE THE MAIN HEADQUARTERS ADDRESS
 ON PLANS/TITLE BLOCKS FOR COORDINATION WITH STATE
 SITE.
 IF SHEETS DO NOT NEED TO BE REVISED FOR OTHER COMMENTS
 THEN PLEASE KNOW THIS CAN BE ADDED TO TITLE BLOCKS BY
 HAND.
 FAC 61G15-23.002
  
 4) NOTE: PLEASE SEE VALUE FOR SCOPE OF WORK WAS NOT
 ADJUSTED.
 PLEASE SEE THAT ALL LABOR, ALL MATERIALS, ALL
 EQUIPMENT; DESIGN COST ETC EVEN IF ANY OF THESE ARE
 OWNER SUPPLIED IS TO BE INCLUDED IN PERMIT
 APPLICATION.
 FBC 108.3
  
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  