| 2007-12-03 16:13:50 | |
| | |
| | ** DENIED REVIEW ** |
| | |
| | ** PLEASE SEE THERE ARE NOTES FROM PREVIOUS REVIEW |
| | WHICH ARE STILL IN NEED OF ADDRESSING ALONG WITH NEW |
| | NOTES. |
| | |
| | |
| | |
| | 1) NOTE:PLEASE SEE THE MANUFACTURES SPECS/CUT SHEETS |
| | HAVE NOT BEEN SUBMITTED FOR EQUIPMENT INCLUDING |
| | TRANSFER SWITCH(S) AS REQUESTED ON PREVIOUS REVIEW. |
| | AS EACH SITE IS *SITE SPECIFIC* EACH SET OF PLANS AND |
| | RECORD DOCUMENTS ARE REQUIRED TO BE SITE SPECIFIC TO |
| | EACH LOCATION. |
| | 110.3, 90.7 |
| | FBC 106.1.2 |
| | |
| | 2) NOTE: PLEASE SEE FS 365.172. PLEASE PROVIDE |
| | DOCUMENTATION AS TO WHETHER OR NOT THE BACK UP SYSTEM |
| | IS PART OF A E-911 SYSTEM. |
| | PLEASE SEE NFPA-1221 CHAPTER 4 AS THIS WOULD REQUIRE |
| | BACK UP POWER FOR ANY LEGALLY REQUIRED SYSTEM. |
| | IF THE BACK UP SYSTEM IS REQUIRED BY LAW PLEASE PROVIDE |
| | DOCUMENTS AND PLANS ACCORDINGLY. |
| | PLEASE ALSO SEE TITLE 47 OF THE FEDERAL US CODE. |
| | THIS IS A NEW NOTE AND CLARIFICATION OF SYSTEM IS |
| | NEEDED. |
| | |
| | 3) NOTE: PLEASE PROVIDE THE MAIN HEADQUARTERS ADDRESS |
| | ON PLANS/TITLE BLOCKS FOR COORDINATION WITH STATE |
| | SITE. |
| | IF SHEETS DO NOT NEED TO BE REVISED FOR OTHER COMMENTS |
| | THEN PLEASE KNOW THIS CAN BE ADDED TO TITLE BLOCKS BY |
| | HAND. |
| | FAC 61G15-23.002 |
| | |
| | 4) NOTE: PLEASE SEE VALUE FOR SCOPE OF WORK WAS NOT |
| | ADJUSTED. |
| | PLEASE SEE THAT ALL LABOR, ALL MATERIALS, ALL |
| | EQUIPMENT; DESIGN COST ETC EVEN IF ANY OF THESE ARE |
| | OWNER SUPPLIED IS TO BE INCLUDED IN PERMIT |
| | APPLICATION. |
| | FBC 108.3 |
| | |
| | |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |