Plan Review Notes
Plan Review Notes For Permit 07090403
Permit Number 07090403
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-10-22 16:16:121. NO ELECTRICAL CONDUITS SHALL ENTER ANY OF THE
 REQUIRED EXIT STAIRTOWERS. PLEASE PROVIDE A NOTE ON THE
 PLANS THAT NO CONDUITS SHALL BE CHASED THROUGH ANY EXIT
 STAIRTOWER EITHER VERTICALLY OR HORIZONTALLY.
  
 2. ANY PROPOSED INSTALLATION OF EQUIPMENT SHALL NOT
 INTERFERE WITH ANY EXISTING FIRE PROTECTION SYSTEMS OR
 DEVICES.
  
 3. ANY EQUIPMENT INSTALLED ON THE ROOF SHALL NOT
 INTERFERE WITH ANY STANDPIPE ROOF MANIFOLDS.
  
 4. ALL CONSTRUCTION, DEMOLITION, AND RENOVATION WORK TO
 COMPLY WITH NFPA 241.
  
 5. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY.
  
 6. EXITS SHALL REMAIN CLEAR AND UNOBSTRUCTED DURING
 WORK ACTIVITIES.
  
 7. ANY PENETRATIONS EITHER VERTICALLY OR HORIZONTALLY
 WITHIN RATED FIRE RATED ASSEMBLIES SHALL BE PROPERLY
 SEALED TO PREVENT FIRE, SMOKE OR HEATED FIRE GASES FROM
 SPREADING.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 804-4709 PHONE
 804-4774 FAX