Plan Review Notes
Plan Review Notes For Permit 07090403
Permit Number 07090403
Review Stop E
Sequence Number 1
Notes
Date Text
2007-10-06 17:36:14 
 *** DENIED***
  
 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2003 NFPA-101
  
 ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED
 FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS
 NOT MADE BY OTHER TRADE(S).
  
 2) NOTE: PLEASE SEE THE PROPOSED LOCATIONS OF EQUIPMENT
 AND ELECTRICAL CONDUITS IN ANY STAIRWAYS ARE STRICTLY
 PROHIBITED. PLEASE SEE FBC CHAPTER 10 AND BUILDING
 REVIEW AND FIRE MARSHAL REVIEW NOTES.
 THIS IS BEING NOTED AT THIS TIME FOR INFORMATION.
  
 3) NOTE: PLEASE KNOW THE ADDITIONAL SERVICE AS SHOWN
 AND PROPOSED IS NOT GRANTED AT THIS TIME PER 230.2.
 PLEASE SEE THE LOCATION OF ALL DISCONNECTING MEANS FOR
 POWER SHALL BE GROUPED. 230.72
 PLEASE CLARIFY WHY THERE ARE TWO 200AMP RECEPTACLE
 SOURCES?SEEMS TO SHOW ONE AT ROOF AND ONE AT GROUND
 LEVELS?
 THERE ARE NO NOTES FOR SIGNAGE ETC.
 PLEASE KNOW AT THIS TIME DUE TO THE SERVICE EQUIPMENT
 BEING CHANGED ETC, THERE MAY BE NEW NOTES ON THE
 FOLLOWING REVIEW.
  
 4) NOTE: PLEASE SUBMIT MANUFACTURES SPECS/CUT SHEETS
 FOR WHAT APPEARS TO BE A MANUAL TRANSFER SWITCH/
 *WALKING BEAM* BREAKER.
 PLEASE SUBMIT A COMPLETE PACKAGE FOR PROPOSED EQUIPMENT
 AND PLEASE BE SURE ALL EQUIPMENT CONTAINS THE REQUIRED
 LISTINGS PER A NATIONALLY RECOGNIZED TESTING LABORATORY
 (NRTL)>
 110.3, 90.3.
 FBC 106.1.2
  
 5) NOTE: PLEASE ADJUST INFORMATION ON TITLE BLOCKS FOR
 KCI AS THE ADDRESS INFORMATION AS LISTED WITH THE
 DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION IS
 NOT THAT AS LISTED ON PLANS.
 FAC 61G11-16.004
 PLEASE ALSO SEE THE REQUIRED MISSING COMPLETE
 INFORMATION FOR THE ENGINEER OF RECORD AS SHOWN PER
 61G15-23.002.
 PLEASE SEE THE INFORMATION FOR THE ENGINEER OF RECORD
 IS NOT COMPLETE AT THIS TIME.
  
 6) NOTE: PLEASE SEE THE APPLIED VALUE FOR THE COMPLETE
 SCOPE OF WORK WHICH IS SHOWN ON PLANS IS LOW. PLEASE
 SEE FBC 108.3 AS THE VALUE IS TO INCLUDE ALL LABOR,
 MATERIALS, EQUIPMENT, AND DESIGN COST ETC EVEN IF ANY
 EQUIPMENT IS OWNER SUPPLIED.
  
 7) NOTE: PLEASE SEE THE GROUNDING ELECTRODE SYSTEM AS
 SHOWN DOES NOT MEET 250.50.
  
 8) NOTE: PLEASE PROVIDE WALL/FLOOR PENETRATION DETAIL
 SHEET WITH ALL LISTED DETAILS AS REQUIRED.
 THIS WILL ALSO MOST LIKELY BE A COMMENT FROM
 FIRE/BUILDING.
 PLEASE SEE NEC 300.21.
 ANSI, ASTM, NFPA, UL ETC.
  
 9) NOTE: PLEASE SEE THAT THE ACTUAL ADDRESS OF THE
 SCOPE OF WORK IS PLACED ON TEH TITLE BLOCKS. WP1097
 DOES NOT GIVE THE ACURATE RECORD AS NEEDED PER FAC
 61G1-16.004, 61G15-23.002, FBC 110.1.2, 106.1.2
  
 ** AS THERE WILL BE SEVERAL CHANGES, PLEASE BE SURE TO
 GO OVER COMMENTS FROM ALL TRADES WHICH MAY AFFECT THE
 SCOPE OF WORK ALONG WITH OTHER TRADE REVIEWED SHEETS.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH