| Date |
Text |
| 2007-09-28 08:39:22 | DENIED |
| | REFERENCE: |
| | ** FBC-2004 WITH 05 & 06 REVISIONS, FUEL GAS. |
| | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| | REQUIREMENTS. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE. |
| | ** FLORIDA STATUTES. |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATIONREQUIRED FOR GAS |
| | PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | NOTE: NOT ALL CORRESPONDING LENGTHS OF THE CUT SECTIONS |
| | ARE GIVEN FOR THE PROPOSED POOL HEATER. THE ONLY |
| | CORRESPONDING LENGTH FOR THE PROPOSED POOL HEATER IS |
| | FOR THE UNDERGROUND PE PIPE. WHAT ARE THE CORRESPONDING |
| | LENGTHS OF THE ABOVE GROUN PIPING. |
| | |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | NOTE: NOT ALL MATERIAL TYPES OR PIPE SIZES ARE BEING |
| | INDICATED FOR THE PROPOSED POOL HEATER AND NEW TEE FOR |
| | THE POOL HEATER. WHAT IS THE ABOVE GROND PIPING |
| | MATERIAL AND PIPE SIZE FOR THE PROPOSED POOL HEATER AND |
| | THE NEW TEE FOR THE POOL HEATER? |
| | |
| | 3. THE EXISTING 3/4" RISER FEEDING THE WATER HEATER |
| | AND RANGE NEEDS TO INCREASE TO 1" PER TABLE 402.4(2). |
| | |
| | 4. CLEARLY INDICATE THE MODEL NUMBER OF THE POOL |
| | HEATER BEING USED ON THE RESUBMITTED MANUFACTURER |
| | SHEETS. |
| | |
| | 5. A NOTICE OF COMMENCEMENT IS REQUIRED-PALM BEACH |
| | COUNTY COURTHOUSE-4TH FLOOR RECORDING DEPT. BEFORE THE |
| | PERMIT IS ISSUED. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL: [email protected] |