| 2008-02-25 15:27:33 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. PROVIDE TWO COPIES OF A SITE PLAN WITH THE |
| | FOLLOWING INFORMATION. |
| | |
| | A} POINT OF CONNECTION LOCATION OF THE PROPOSED 3/4" |
| | WATER SERVICE TO THE PROPOSED NEW FINGER DOCK BEING |
| | INDICATED ON THE ELECTRICAL PLAN. PER FBC PLUMBING |
| | SECTION *601.1 SCOPE. |
| | |
| | B} LOCATION OF THE REQUIRED RPZV BACKFLOW PREVENTER |
| | (NOTE: THE RPZV BACKFLOW PREVENTER MUST BE INSTALLED ON |
| | PRIVATE PROPERTY AS CLOSE TO THE SOURCE OF SUPPLY (NEW |
| | FINGER DOCK) AS POSSIBLE). PER FBC PLUMBING SECTION |
| | *608.1 GENERAL. |
| | |
| | C} CLEARLY INDICATE THE PIPING MATERIAIL OF THE |
| | PROPOSED WATER SERVICE TO THE NEW FINGER DOCK AS WELL |
| | AS TO THE INLET AND OUTLET OF THE REQUIRED RPZV |
| | BACKFLOW PREVENTER. PER FBC PLUMBING SECTION *601.1 |
| | SCOPE. |
| | |
| | D} CLEARLY INDICATE IF THE DOCK IS GOING TO HAVE HOSE |
| | CONNECTIONS (SILLCOCK, HOSE BIBB, WALL HYDRANT OR OTHER |
| | TYPE OF HOSE CONNECTION) AND THE LOCATION OF THE HOSE |
| | CONNECTION AND THAT THE HOSE CONNECTIONS WILL BE |
| | PROTECTED BY AN ATMOSPHERIC-TYPE VACUUM BREAKER. PER |
| | FBC PLUMBING SECTION *601.1 SCOPE AND SECTION |
| | 608.15.4.2 HOSE CONNECTIONS. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |