| 2007-12-03 06:49:17 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | | NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1}THE LOAD BEING SERVED BY THE GENERATOR, (86.33 | | | AMPS) IS LARGER THAN THE GENERATOR OUTPUT (75 AMPS). | | | SEE 702.5 CAPACITY AND RATING | | | AN OPTIONAL STANDBY SYSTEM SHALL HAVE ADEQUATE CAPACITY | | | AND RATING FOR THE SUPPLY OF ALL EQUIPMENT INTENDED TO | | | BE OPERATED AT ONE TIME. OPTIONAL STANDBY SYSTEM | | | EQUIPMENT SHALL BE SUITABLE FOR THE MAXIMUM AVAILABLE | | | FAULT CURRENT AT ITS TERMINALS. THE USER OF THE | | | OPTIONAL STANDBY SYSTEM SHALL BE PERMITTED TO SELECT | | | THE LOAD CONNECTED TO THE SYSTEM. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|