| Plan Review Notes For Permit 07090360 |
| Permit Number |
07090360 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-10-01 16:38:52 | DENIED | | | REFERENCE: | | | ** FBC-2004 WITH 05 &O6 REVISONS, FUEL GAS. | | | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION | | | REQUIREMENTS. | | | ** FBC-2004 CHAPTER 1, THE CITY OF | | | WEST PALM BEACH AMENDMENTS. | | | ** FLORIDA ADMINISTRATIVE CODE. | | | ** FLORIDA STATUTES. | | | | | | THE FOLLOWING CORRECTION/INFORMATION IS REQUIRED FOR | | | GAS PLAN REVIEW TO MEET CODE COMPLIANCE: | | | | | | 1. PER FBC-2004 W/O5 & 06 REV, TABLE 402.4(2) THE | | | ABOVE GROUND SCH 40 METALLIC PIPING NEEDS TO BE 1 INCH | | | (1"). PLEASE PROVIDE MANUFACTURER'S SPECIFICATIONS OF A | | | 1 INCH SCH 40 METALLIC TO 3/4 INCH PE TRANSITION OR | | | CHANGE ALL PIPE SIZES TO BE 1 INCH ON THE RESUBMITTAL. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] |
|