Plan Review Notes
Plan Review Notes For Permit 07090360
Permit Number 07090360
Review Stop G
Sequence Number 1
Notes
Date Text
2007-10-01 16:38:52DENIED
 REFERENCE:
 ** FBC-2004 WITH 05 &O6 REVISONS, FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTION/INFORMATION IS REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. PER FBC-2004 W/O5 & 06 REV, TABLE 402.4(2) THE
 ABOVE GROUND SCH 40 METALLIC PIPING NEEDS TO BE 1 INCH
 (1"). PLEASE PROVIDE MANUFACTURER'S SPECIFICATIONS OF A
 1 INCH SCH 40 METALLIC TO 3/4 INCH PE TRANSITION OR
 CHANGE ALL PIPE SIZES TO BE 1 INCH ON THE RESUBMITTAL.
  
 END OF COMMENTS:
  