Plan Review Notes
Plan Review Notes For Permit 07090359
Permit Number 07090359
Review Stop E
Sequence Number 2
Notes
Date Text
2008-01-07 07:57:59 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 THIS COMMENT FROM THE PREVIOUS REVIEW.
  
 PER R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. WHEN
 INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE PROVIDED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE ALARMS
 SHALL BE INTERCONNECTED AND HARD WIRED. INDICATE
 LOCATION OF SMOKE ALARMS ON THE PLANS.* THIS COMMENT
 WAS MADE TO DETERMINE COMPLIANCE WITH THE ARTICLE, A
 SMOKE ALARM IS NOT REQUIRED IN THE ADDITION.
  
 THE ELECTRICLE PLANS SUBMITTED ARE ON SHEET A-1.0, THE
 ARCHITECTURAL PLANS ARE ON A SHEET MARKED A-1.0. FOR
 RECORD RETENTION SEPERATLY NUMBER THE SHEETS, AND
 ASSEMLE THE SHEETS INTO TWO SETS. 106.1.6 FBC AS
 AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]