Plan Review Notes
Plan Review Notes For Permit 07090359
Permit Number 07090359
Review Stop B
Sequence Number 2
Notes
Date Text
2008-01-15 18:15:35 
  
  
 DENIED
  
 THE FOLLOWING COMMENTS WERE NOT ADDRESS FROM THE 1ST
 REVIEW:
  
 1)THE 2006 AMENDMENTS TO THE 2004 FBC REQUIRE
 BUILDINGS LOCATED WITHIN EXP B TYPE TERRAIN THAT IS
 DIRECTLY ADJACENT TO EXP C TYPE TERRAIN SUCH AS OPEN
 GOLF COURSES AND BODIES OF WATER FOR A DISTANCE OF 600
 FEET OR MORE IN ANY QUADRANT TO BE IN AN EXP C
 CATEGORY. PLEASE ADJUST THE DESIGN PARAMETERS AND WIND
 PRESSURES ACCORDINGLY.*** BE SURE TO CHECK PRODUCT
 APPROVALS FOR COMPLIANCE WITH INCREASED DESIGN
 PRESSURE***
 *********NOTE THIS IS AN EXPOSURE C PLEASE ADJUST WIND
 INFORMATION AND OPENING DESIGN PRESSURES*********
  
 2)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF
 EACH PRODUCT APPROVAL THATIS RELEVANT PER 9B-72.
 THESE SHOULD INCLUDE THE FLORIDA STATE APPROVAL COVER
 PAGES, AND THE PRODUCT NOA THAT LISTS THE SYSTEM
 COMPONENTS/ FASTENER LIST PAGES. ALL CAN BE FOUND ON
 WWW.FLORIDABUILDING.ORG ****PROVIDE PRODUCT
 APPROVALS FOR THE CASTCRETE LINTELS, CONNECTOR
 STRAPS/TIES, ETC.****
 ***********NOTE PROVIDE LINTEL AND CONNECTOR PRODUCT
 APPROVAL SHEETS, ALSO NOTE THAT SEVERAL DIFFERENT
 PRODUCT APPROVALS WERE SUBMITTED IN PACKAGE FOR WINDOWS
 AND DOORS . PLEASE SUBMIT ONLY 2 COPIES OF EACH PRODUCT
 THAT WILL BE USED MAKING SURE THAT THEY ARE LEDGIBLE
 AND EACH IS REVIEWED AND APPROVED FOR USE BY THE
 DESIGNER OF RECORD***********
  
 3)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 9)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT
 SETS OF PLANS MUST BE STAMPED BY THAT OFFICE, AND A
 COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 10)SHOW THAT NEW ROOF/CEILING THAT HAS BECOME PART OF
 CONDITIONED SPACE WILL RECEIVE INSULATION
 **********NOTE SUBMIT TWO COPIES OF ENERGY CALC'S PER
 13-101.2.2 FBC. BE SURE THAT THEY ARE SIGNED AND DATED
 BY PREPARER AND OWNER/AGENT PRIOR TO SUBMITTAL. SMALL
 ADDITIONS UNDER 600 SQ. FT CAN USE SHORT FORM 600C-04R
 BUT PLEASE NOTE THAT R30 MUST BE INSTALLED IN CEILING
 ATTIC AND BLOCK WALL REQUIRE A MINIMUM R7***********
  
 11)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
  
 NEW COMMENTS:
  
 1)IF WINDOWS AND DOORS THAT ARE BEING INSTALLED IN
 THE NEW ADDITION ARE NOT IMPACT RESISTANT PLEASE SUBMIT
 PRODUCT APPROVALS AND INSTALLATION SCHEDULE FOR
 PROTECTIVE DEVICES. SEE ATTACHED CITY MEMO AND
 SCHEDULE
  
 2)REMOVE ALL OLD PAGES AND RESUBMIT 2 COMPLETE SETS
 OF NEW DRAWINGS WITH REVISIONS AND INCLUDE 1 COPY OF
 THE OLD PAGES ONLY FOR REFERENCE. PLEASE ASSEMBLE ALL
 SIGNED AN SEALED DRAWINGS THAT PERTAIN TO WORK BEING
 PERFORMED, TOGETHER IN COMPLETE SETS AND SUBMIT WITH
 ONLY 1 SET OF REFERENCE DRAWINGS. PLEASE SUBMIT
 REQUIRED DOCUMENTS FOR ALL OTHER REVIEWERS
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716