2007-09-19 15:20:56 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 NO ELECTRICAL PLANS WERE SUBMITTED, AND NO ELECTRICAL
 CONTRACTOR IS SIGNED ON, HOWEVER RECEPTACLES ARE
 REQUIRED PER 210.52 ANSD LIGHTING PER 210.70. AN
 ELECTRICAL PERMIT IS REQUIRED.
  
 PER R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. WHEN
 INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE PROVIDED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE ALARMS
 SHALL BE INTERCONNECTED AND HARD WIRED. INDICATE
 LOCATION OF SMOKE ALARMS ON THE PLANS
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  