| Plan Review Notes For Permit 07090344 |
| Permit Number |
07090344 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-09-14 08:25:14 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | | | | | SHUTTER PERMIT APPLICATION, ONLY CHECKED ITEMS APPLY | | | | | | ____1.PROVIDE BUILDING HEIGHT ON THE PLAN.DESIGN | | | PRESSURES FOR BUILDINGS OVER 60FEET ARE REQUIRED TO BE | | | DESIGNED USING ASCE7, FBC1609.1.1 AND MUST BE DONE BY A | | | DESIGN PROFESSIONAL. DOCUMENTS PREPARED BY AN ARCHITECT | | | OR ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE | | | SIGNED SEALED ORIGINALS FAC61G15, FAC61G1 16. | | | | | | ____2.PROVIDE A COPY OF THE CONDO ASSOCIATION | | | APPROVAL. | | | | | | _XX_3.COMPLETE THE ATTACHED INSTALLATION SCHEDULE | | | OR PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN | | | ANOTHER FORMAT, FBC*106. | | | | | | ____4.FLORIDA STATE OR LOCAL PRODUCT APPROVAL | | | REQUIRED, FAC9B72, WWW.FLORIDABUILDING.ORG. | | | | | | ____5.SHOW THE EMERGENCY MEANS OF ESCAPE, FBC | | | R310. | | | | | | ____6.PROVIDE A FLOOR PLAN SHOWING WHERE THE | | | SHUTTERS WILL BE INSTALLED AND PANEL SIZES WHICH | | | CORRELATES WITH THE INSTALLATION SCHEDULE, ITEM 3 | | | ABOVE. | | | | | | ____8.REVISE EXPOSURE CATEGORY FBC1609.6.2.1(2), | | | FBC R301.2.1.4.NOTE THAT THE DEFINITION FOR EXPOSURE | | | C HAS CHANGED EFFECTIVE DECEMBER 8, 2006 FBC1609.4, FBC | | | R301.2.1.4. |
|