| Date |
Text |
| 2007-09-12 15:23:17 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 |
| | EXISTING BUILDING CODE |
| | FBC*CITY OF WEST PALM BEACH |
| | AMENDMENTS TO THE FBC2004 |
| | |
| | ROOFING PERMIT; ONLY CHECKED ITEMS APPLY |
| | |
| | ____1.)A NOTICE OF COMMENCEMENT MUST BE FILED WITH |
| | THE CLERK OF COURTS PRIOR TO PERMIT PICKUP, FS713.13. |
| | |
| | _XX_2.)CONTRACTOR IS TO PROVIDE THE FOLLOWING |
| | INFORMATION ON THE APPLICATION, SEE ATTACHED POLICY; |
| | MEAN ROOF HEIGHT, ROOF PITCH, ROOF DECK TYPE, AREA OF |
| | EACH ROOF TYPE |
| | |
| | _XX_3.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL |
| | REQUIRED IN ADDITION TO THE EVALUATION REPORT |
| | SUBMITTED, FAC9B72.WWW.FLORIDABUILDING.ORGTHIS |
| | PRODUCT HAS A FLORIDA STATE PRODUCT APPROVAL SO A LOCAL |
| | WILL NOT BE ISSUED.PLEASE PRINT THE FLORIDA STATE |
| | PRODUCT APPROVAL FROM THE WEBSITE. |
| | |
| | PROVIDE THE FIRST SHEETS OF THE NOA WHICH GIVE THE |
| | SYSTEM COMPONENTS. |
| | |
| | ____4.)FOR THE FLAT DECK, SELECT THE APPROVED |
| | ASSEMBLY YOU ARE USING.ALSO INDICATE WHICH FASTENER |
| | YOU ARE USING IF THE OPTIONS HAVE DIFFERENT PRESSURE |
| | LIMITATIONS. |
| | |
| | _X_5.)FOR THE FLAT DECK, SPECIFY THE ENHANCED |
| | FASTENING FOR CORNER AND PERIMETER ZONES.THIS IS TO |
| | BE DONE ON THE PRODUCT APPROVAL (BOTH SETS) OR ON |
| | LETTERHEAD, NOT ON THE RESUB SHEET. |
| | |
| | ____ 6.)ON THE TILE PRODUCT APPROVAL, INDICATE WHICH |
| | METHOD OF ATTACHMENT YOU ARE USING.IF YOU SELECT FOAM |
| | ADHESIVE, PRODUCT APPROVALS REQUIRED FAC9B72. |
| | |
| | ____ 7.)SEE PRODUCT LIMITATION #7.CALCULATIONS |
| | PREPARED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF |
| | CONSULTANT REQUIRED FOR ENHANCED FASTENING. |