Date Text
2007-09-27 14:14:52DENIED
 REFERENCE:
 ** FBC-2004 WITH 05 & 06 REVISIONS SECTIONS 424.2 AND
 R4101 SWIMMING POOLS.
 ** FBC-2004 WITH 05 & 06 REVISIONS, PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SHEET 1 POOL DATA & EQUIPMENT INDICATES THE
 FOLLOWING "HEATER: EXISTING GAS HEATER". PLEASE CLARIFY
 ON THE RESUBMITTAL HOW A NEW POOL AND SPA HAS AN
 EXISTING GAS HEATER.
  
 2. FBC-2004 SEC. 424.2.14.1, OR
 FBCR-2004 SEC. R4101.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. (MANUFACTURE
 SHEETS REQUIRED, PLEASE SUBMIT)
  
 3. FBC-2004 SEC. 424.2.14.2, OR
 FBCR-2004 SEC. R4101.14.2 WATER
 RETENTION, PROVIDE A POSITIVE MEANS OF
 RETAINING WATER IN THE HEATER WHEN PUMP
 IS SHUT OFF.(MANUFACTURE SHEETS
 REQUIRED, PLEASE SUBMIT)
  
 4. FBC-2004 SEC. 424.2.14, OR FBCR-2004
 SEC. R4101.15 GAS PIPING SHALL COMPLY
 WITH FBC FUEL GAS. SEPARATE PLANS AND
 PERMIT REQUIRED.
  
 END OF COMMENTS:
  