Plan Review Notes
Plan Review Notes For Permit 07090336
Permit Number 07090336
Review Stop E
Sequence Number 1
Notes
Date Text
2007-09-18 11:48:52 
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT
 SIZE AND TYPE, GROUNDING DETAILS, , SERVICE EQUIPMENT
 AND PANEL LOCATIONS PER 106.3.5.4 FBC.
  
 2} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT
 CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE
 EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS
 EQUAL TO OR GREATER THAN THE AVAILABLE FAULT.
  
 3} PROVIDE A SITE PLAN INDICATING THE LOCATION OF ALL
 SERVICE EQUIPMENT SO THAT COMPLIANCE WITH ARTICLE 230
 CAN BE REVIEWED. THIS PROPERTY HAS 2 LEGAL RESIDENCES.
 INDICATE WHERE THE DUPLEX METER IS TO BE INSTALLED AND
 IF THERE NOW WOULD BE THREE METERS ON THIS PROPERTY.
 LOCATE ALL EQUIPMENT (INCLUDING PANEL LOCATIONS) ON THE
 SITE PLAN. DISCONNECTS NOT SHOWN ON THE PLAN MAY BE
 REQUIRED PER 230.70(A)(1).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]