| 2007-12-17 11:26:23 | *****DENIED***** |
| | |
| | THE FOLLOWINGS COMMENTS TAKEN FROM THE PREVIOUS FIRE |
| | PLAN REVIEW STILL NEED TO BE ADDRESSED: |
| | |
| | 2.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE |
| | REFERENCED. |
| | |
| | 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 4.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL |
| | BE REMOVED FROM THE SITE DAILY OR MORE FREQUENTLY AS |
| | NECESSARY FOR SAFE OPERATION. |
| | |
| | 5.THE REMOVAL OF OLD AND/OR THE STOCKING OF NEW |
| | BUILDING MATERIALS & SUPPLIES SHALL NOT HINDER OR |
| | INTERFERE WITH ACCESS TO OR EGRESS FROM THE OTHER |
| | TENANT SPACES ON THE 15TH FLOOR OR THE BUILDING. |
| | |
| | 7.SPECIFY THE NEW INTERIOR WALL AND CEILING FINISH |
| | MATERIAL IN TERMS OF CLASS A, CLASS B, OR CLASS C. |
| | |
| | 8.PLEASE INDICATE IF THE BUILDING IS SPRINKLERED AND |
| | IF SO, WILL THE SCOPE WORK CAUSE ANY SPRINKLER |
| | MODIFICATIONS.BE ADVISED THAT SEPARATE PLANS AND |
| | PERMIT WILL BE REQUIRED FOR SPRINKLER SYSTEM REMODEL. |
| | |
| | 9.PLEASE INDICATE IF THE BUILDING/RESIDENCE HAS A |
| | FIRE ALARM SYSTEM AND IF SO, WILL THE SCOPE OF WORK |
| | CAUSE ANY FIRE ALARM DEVICE(S) MODIFICATIONS.BE |
| | ADVISED THAT SEPARATE PLANS AND PERMIT WILL BE REQUIRED |
| | FOR THE FIRE ALARM REMODEL. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS |
| | ADDRESSED.PLEASE BE ADVISED THAT THE HAND WRITTEN |
| | RESPONSES ON THE PLANS ARE NOT ACCEPTABLE!!!!! |
| | |
| | |