| 2007-12-04 11:01:11 | ** DENIED 3RD REVIEW ** |
| | |
| | ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ARE |
| | STILL IN NEED OF ADDRESSING ALONG WITH SOME NEW |
| | COMMENTS BASED ON REVISED PLANS/INFORMATION ETC. |
| | SOME INFORMATION NOW SHOWN WAS NOT ON PREVIOUS PLANS |
| | THEREFORE A REVIEW OF SOME OF THESE ITEMS COULD NOT |
| | HAVE BEEN DONE. |
| | |
| | ** SOME OF THESE COMMENTS BELOW COULD HAVE BEEN |
| | REDLINED HOWEVER NOT ALL. |
| | |
| | 1) NOTE: PLEASE COMPLETE CIRCUITING ON PLANS; PLEASE |
| | SEE MISSING CIRCUITING FOR SMOKE ALARMS AND ARC FAULT |
| | REQUIRED. |
| | PLEASE ALSO SEE MISSING CIRCUIT ON MASTER BEDROOM |
| | RECEPTACLE. |
| | 210.12, 408.4, 240.4 |
| | FBC 106.3.5.1.2 |
| | REQUESTED ON TWO PREVIOUS REVIEWS IN NOTES #3, #4 AND |
| | #5. |
| | |
| | 2) NOTE: PLEASE SEE BEDROOM #2 AS STATED ON PREVIOUS |
| | REVIEW NOTE # 7 WILL REQUIRE A LIGHT FIXTURE. THE |
| | RESPONSE MENTIONS TO SEE NOT AT THE TOP OF PLAN PAGE. |
| | THE NOTE ON PLANS IS FOR THE BALCONY LIGHTS. THE |
| | BALCONY ON A MULTI-STORY BUILDING IS NOT REQUIRED TO |
| | HAVE LIGHTING UNDER THE CURRENT CODE AS THERE IS NO |
| | GROUND LEVEL ACCESS. THIS NOTE WAS ONLY FOR A FIXTURE |
| | OF SOME TYPE IN BEDROOM #2. THIS COULD HAVE BEEN |
| | REDLINED HOWEVER OTHER COMMENTS NEED TO BE ADDRESSED. |
| | |
| | 3) NOTE: PLEASE SEE THE CODE REFERENCED ON THE LOAD |
| | CALCULATIONS IS NOT FROM THE 2005 NEC. THE CALCULATIONS |
| | FOR EXISTING IS FROM 220.87 |
| | THIS ALSO COULD HAVE BEEN REDLINED AS NOT SHOWING THE |
| | CORRECT CODE HOWEVER SEE THE FOLLOWING COMMENT. |
| | |
| | 4) NOTE: PLEASE SEE THE LOAD CALCULATIONS STATE AND |
| | SHOW A NEW STEAM UNIT HOWEVER NO INFORMATION IS SHOWN |
| | ON PLANS, NO LOCATION, NO LISTING ON PANEL SCHEDULE, NO |
| | OVER CURRENT PROTECTION, NO CONDUCTORS ETC. |
| | PLEASE PROVIDE CUT SHEETS ON UNIT WHICH CONTAIN A |
| | LISTING FROM A NATIONALLY RECOGNIZED TESTING |
| | LABORATORY. |
| | THIS UNIT WAS NOT ON PREVIOUS PLANS OR LOAD |
| | CALCULATIONS. |
| | 110.3, 90.7, 408.4, 310.16, 240.4 ETC |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |