Plan Review Notes
Plan Review Notes For Permit 07090326
Permit Number 07090326
Review Stop E
Sequence Number 3
Notes
Date Text
2007-12-04 11:01:11** DENIED 3RD REVIEW **
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING ALONG WITH SOME NEW
 COMMENTS BASED ON REVISED PLANS/INFORMATION ETC.
 SOME INFORMATION NOW SHOWN WAS NOT ON PREVIOUS PLANS
 THEREFORE A REVIEW OF SOME OF THESE ITEMS COULD NOT
 HAVE BEEN DONE.
  
 ** SOME OF THESE COMMENTS BELOW COULD HAVE BEEN
 REDLINED HOWEVER NOT ALL.
  
 1) NOTE: PLEASE COMPLETE CIRCUITING ON PLANS; PLEASE
 SEE MISSING CIRCUITING FOR SMOKE ALARMS AND ARC FAULT
 REQUIRED.
 PLEASE ALSO SEE MISSING CIRCUIT ON MASTER BEDROOM
 RECEPTACLE.
 210.12, 408.4, 240.4
 FBC 106.3.5.1.2
 REQUESTED ON TWO PREVIOUS REVIEWS IN NOTES #3, #4 AND
 #5.
  
 2) NOTE: PLEASE SEE BEDROOM #2 AS STATED ON PREVIOUS
 REVIEW NOTE # 7 WILL REQUIRE A LIGHT FIXTURE. THE
 RESPONSE MENTIONS TO SEE NOT AT THE TOP OF PLAN PAGE.
 THE NOTE ON PLANS IS FOR THE BALCONY LIGHTS. THE
 BALCONY ON A MULTI-STORY BUILDING IS NOT REQUIRED TO
 HAVE LIGHTING UNDER THE CURRENT CODE AS THERE IS NO
 GROUND LEVEL ACCESS. THIS NOTE WAS ONLY FOR A FIXTURE
 OF SOME TYPE IN BEDROOM #2. THIS COULD HAVE BEEN
 REDLINED HOWEVER OTHER COMMENTS NEED TO BE ADDRESSED.
  
 3) NOTE: PLEASE SEE THE CODE REFERENCED ON THE LOAD
 CALCULATIONS IS NOT FROM THE 2005 NEC. THE CALCULATIONS
 FOR EXISTING IS FROM 220.87
 THIS ALSO COULD HAVE BEEN REDLINED AS NOT SHOWING THE
 CORRECT CODE HOWEVER SEE THE FOLLOWING COMMENT.
  
 4) NOTE: PLEASE SEE THE LOAD CALCULATIONS STATE AND
 SHOW A NEW STEAM UNIT HOWEVER NO INFORMATION IS SHOWN
 ON PLANS, NO LOCATION, NO LISTING ON PANEL SCHEDULE, NO
 OVER CURRENT PROTECTION, NO CONDUCTORS ETC.
 PLEASE PROVIDE CUT SHEETS ON UNIT WHICH CONTAIN A
 LISTING FROM A NATIONALLY RECOGNIZED TESTING
 LABORATORY.
 THIS UNIT WAS NOT ON PREVIOUS PLANS OR LOAD
 CALCULATIONS.
 110.3, 90.7, 408.4, 310.16, 240.4 ETC
 FBC 106.1.2, 106.3.5.1.2
  
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]