Plan Review Notes
Plan Review Notes For Permit 07090326
Permit Number 07090326
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2007-11-03 17:17:58*****DENIED*****
  
 THE FOLLOWINGS COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN REVIEW STILL NEED TO BE ADDRESSED:
  
 2.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 4.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE DAILY OR MORE FREQUENTLY AS
 NECESSARY FOR SAFE OPERATION.
  
 5.THE REMOVAL OF OLD AND/OR THE STOCKING OF NEW
 BUILDING MATERIALS & SUPPLIES SHALL NOT HINDER OR
 INTERFERE WITH ACCESS TO OR EGRESS FROM THE OTHER
 TENANT SPACES ON THE 15TH FLOOR OR THE BUILDING.
  
 6.PLEASE SHOW THE LOCATION OF THE SMOKE ALARMS (SA)
 IN THIS RESIDENCE.PLEASE BE ADVISED THAT SMOKE ALARMS
 (SA)SOUND ONLY WITHIN AN INDIVIDUAL DWELLING UNIT,
 WHEREAS SMOKE DETECTORS (SD) ARE TIED INTO THE
 BUILDING'S FIRE ALARM SYSTEM.
  
 7.SPECIFY THE NEW INTERIOR WALL AND CEILING FINISH
 MATERIAL IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 8.PLEASE INDICATE IF THE BUILDING IS SPRINKLERED AND
 IF SO, WILL THE SCOPE WORK CAUSE ANY SPRINKLER
 MODIFICATIONS.BE ADVISED THAT SEPARATE PLANS AND
 PERMIT WILL BE REQUIRED FOR SPRINKLER SYSTEM REMODEL.
  
 9.PLEASE INDICATE IF THE BUILDING/RESIDENCE HAS A
 FIRE ALARM SYSTEM AND IF SO, WILL THE SCOPE OF WORK
 CAUSE ANY FIRE ALARM DEVICE(S) MODIFICATIONS.BE
 ADVISED THAT SEPARATE PLANS AND PERMIT WILL BE REQUIRED
 FOR THE FIRE ALARM REMODEL.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722