Plan Review Notes
Plan Review Notes For Permit 07090326
Permit Number 07090326
Review Stop E
Sequence Number 2
Notes
Date Text
2007-10-31 12:26:39 
 ** DENIED 2ND REVIEW**
  
 ** PLEASE SEE NOTES FROM PREVIOUS REVIEW WHICH IS STILL
 IN NEED OF ADDRESSING.
 PLEASE SEE MOST OF THE NOTES BELOW WERE TAKEN FROM
 PREVIOUS REVIEW.
  
  
 1) NOTE:THIS IS THE SAME NOTE:
 PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH ARE
 SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE. PLEASE SEE
 THAT THIS SHALL INCLUDE 2006 REVISIONS TO THE 2004 FBC
 FOR ALL TRADES AND THE 2005 NFPA-70. PLEASE KNOW THERE
 ARE CHANGES IN THE FBC WHICH MAY AFFECT DESIGNS FOR ALL
 TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 2) NOTE:THIS IS THE SAME NOTE: IN FACT PLEASE SEE
 ELECTRICAL PLANS NOW CONTAIN A NOTE FROM THE ENGINEER
 WHICH SPECIFICALLY STATES THE ELECTRICAL IS DONE BY
 OTHER YET THIS SAME ENGINEER HAS SIGNED, DATED AND
 SEALED PLANS. IF THE ELECTRICAL DESIGN IS NOT DONE BY
 THIS ENGINEER, THEN ARE STATED IN THE FLORIDA STATUTES,
 HE MAY NOT SIGN, DATE AND SEAL SAID PLANS.
 PLEASE SEE THE *DESIGNER* AS LISTED ON PLANS* MUST MEET
 THE EXCEPTIONSAS SPECIFIED IN THE FLORIDA STATUTES.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE NO DESIGN PROFESSIONAL IS PRINTED, SIGNED,
 OR SIGNED, DATED AND SEALED ON PLANS. PLEASE SEE
 MISSING INFORMATION FOR TITLE BLOCKS IF DONE BY A
 DESIGN PROFESSIONAL UNDER FS 481, 471 PER FAC
 61G15-23.002, 61G1-16.004.
 PLEASE KNOW EVEN WHEN MEETING ANY EXCEPTIONS UNDER FS
 471.003, OR 481.229 A DESIGNER OF RECORD IS STILL
 REQUIRED TO PRINT NAME AND SIGN PLANS.
 FBC 106.1.2, 106.3, 106.5
  
 3) NOTE:THIS IS THE SAME NOTE:IN FACT PLEASE SEE
 THE PANEL SCHEDULE SUBMITTED IS NOT COMPLETE WITH THE
 OVER CURRENT PROTECTION OR MINIMUM CONDUCTOR SIZES.
 THIS WILL ALSO BE NOTED IN COMMENTS BELOW.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE COMPLETE ALL CIRCUITING ON PLANS FOR NEW AND
 CORRELATE WITH A NEW REVISED PANEL SCHEDULE TO BE
 SUBMITTED. THE EXISTING CIRCUITS ONLY NEED BE SHOWN
 WITH AN *E*.
 PLEASE SEE THE PANEL SCHEDULE IS TO INDICATE ALL NEW
 DEDICATED CIRCUITS AS NOTED BELOW.
 FBC 106.3.5.4
 408.4,240.4,310.16,408.4 ETC
  
 4) NOTE: PLEASE SEE THE SMOKE DEVICES WHICH ARE SHOWN
 ARE BEING INDICATED AS *SD* FOR SMOKE DETECTORS. IF
 THESE ARE TRUE SMOKE DETECTORS BY DEFINITION, PLEASE
 INCLUDE THE FIRE ALARM PANEL, HORN DEVICES ETC.
 IF SMOKE ALARMS, PLEASE CHANGE.
  
 ** PREVIOUS REVIEW NOTE **PLEASE SEE MISSING SMOKE
 DETECTION DEVICES AS REQUIRED UNDER FBC R313, AND
 NFPA-72 11.5.1.1, 11.8.3. THE PLANS NEED TO SHOW NEW OR
 EXISTING SMOKE ALARM DEVICES.
 5) NOTE:ARC FAULT INDICATED ON PANEL SCHEDULE HOWEVER
 AS CIRCUITING IS NOT ON PLANS FOR NEW ITEMS, THIS CAN
 NOT BE VERIFIED.
 PLEASE SEE 210.12 AND LIST.
  
 6) NOTE:THIS NOTE REMAINS AS WIRE SIZE AND OVER
 CURRENT PROTECTION ARE NOT SHOWN ON PANEL SCHEDULE.
 PLEASE ALSO SEE CIRCUITING ON PLANS.
 PLEASE BE SURE TO LIST THE REQUIRED DEDICATED
 CIRCUIT(S) FOR BATH RECEPTACLE(S) PER 210.52D,
 210.11C3.
 (MUST BE 20AMP AND #12)
  
 7) NOTE:THIS WAS NOTE #8 ON PREVIOUS REVIEW.
 PLEASE KNOW BEDRM #2 WILL REQUIRE SOME SORT OF LIGHT
 FIXTURE FOR EGRESS INTO THIS ROOM PER 210.70, LS 101
 7.8
  
 8) NOTE: THIS WAS NOTE #10 ON PREVIOUS REVIEW.
 PLEASE SEE MISSING DEDICATED LOAD FOR NEW REFRIGERATOR
 ON LOAD CALCULATIONS.
 220.
 (LIST ON PANEL SCHEDULE).
  
 9) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE.
 THIS IS ONLY A NOTICE GIVEN AT THIS TIME.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]