| | ** DENIED 2ND REVIEW** |
| | |
| | ** PLEASE SEE NOTES FROM PREVIOUS REVIEW WHICH IS STILL |
| | IN NEED OF ADDRESSING. |
| | PLEASE SEE MOST OF THE NOTES BELOW WERE TAKEN FROM |
| | PREVIOUS REVIEW. |
| | |
| | |
| | 1) NOTE:THIS IS THE SAME NOTE: |
| | PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH ARE |
| | SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS |
| | UNDER THE NEW CODES ADOPTED BY THE STATE. PLEASE SEE |
| | THAT THIS SHALL INCLUDE 2006 REVISIONS TO THE 2004 FBC |
| | FOR ALL TRADES AND THE 2005 NFPA-70. PLEASE KNOW THERE |
| | ARE CHANGES IN THE FBC WHICH MAY AFFECT DESIGNS FOR ALL |
| | TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | 2) NOTE:THIS IS THE SAME NOTE: IN FACT PLEASE SEE |
| | ELECTRICAL PLANS NOW CONTAIN A NOTE FROM THE ENGINEER |
| | WHICH SPECIFICALLY STATES THE ELECTRICAL IS DONE BY |
| | OTHER YET THIS SAME ENGINEER HAS SIGNED, DATED AND |
| | SEALED PLANS. IF THE ELECTRICAL DESIGN IS NOT DONE BY |
| | THIS ENGINEER, THEN ARE STATED IN THE FLORIDA STATUTES, |
| | HE MAY NOT SIGN, DATE AND SEAL SAID PLANS. |
| | PLEASE SEE THE *DESIGNER* AS LISTED ON PLANS* MUST MEET |
| | THE EXCEPTIONSAS SPECIFIED IN THE FLORIDA STATUTES. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE NO DESIGN PROFESSIONAL IS PRINTED, SIGNED, |
| | OR SIGNED, DATED AND SEALED ON PLANS. PLEASE SEE |
| | MISSING INFORMATION FOR TITLE BLOCKS IF DONE BY A |
| | DESIGN PROFESSIONAL UNDER FS 481, 471 PER FAC |
| | 61G15-23.002, 61G1-16.004. |
| | PLEASE KNOW EVEN WHEN MEETING ANY EXCEPTIONS UNDER FS |
| | 471.003, OR 481.229 A DESIGNER OF RECORD IS STILL |
| | REQUIRED TO PRINT NAME AND SIGN PLANS. |
| | FBC 106.1.2, 106.3, 106.5 |
| | |
| | 3) NOTE:THIS IS THE SAME NOTE:IN FACT PLEASE SEE |
| | THE PANEL SCHEDULE SUBMITTED IS NOT COMPLETE WITH THE |
| | OVER CURRENT PROTECTION OR MINIMUM CONDUCTOR SIZES. |
| | THIS WILL ALSO BE NOTED IN COMMENTS BELOW. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE COMPLETE ALL CIRCUITING ON PLANS FOR NEW AND |
| | CORRELATE WITH A NEW REVISED PANEL SCHEDULE TO BE |
| | SUBMITTED. THE EXISTING CIRCUITS ONLY NEED BE SHOWN |
| | WITH AN *E*. |
| | PLEASE SEE THE PANEL SCHEDULE IS TO INDICATE ALL NEW |
| | DEDICATED CIRCUITS AS NOTED BELOW. |
| | FBC 106.3.5.4 |
| | 408.4,240.4,310.16,408.4 ETC |
| | |
| | 4) NOTE: PLEASE SEE THE SMOKE DEVICES WHICH ARE SHOWN |
| | ARE BEING INDICATED AS *SD* FOR SMOKE DETECTORS. IF |
| | THESE ARE TRUE SMOKE DETECTORS BY DEFINITION, PLEASE |
| | INCLUDE THE FIRE ALARM PANEL, HORN DEVICES ETC. |
| | IF SMOKE ALARMS, PLEASE CHANGE. |
| | |
| | ** PREVIOUS REVIEW NOTE **PLEASE SEE MISSING SMOKE |
| | DETECTION DEVICES AS REQUIRED UNDER FBC R313, AND |
| | NFPA-72 11.5.1.1, 11.8.3. THE PLANS NEED TO SHOW NEW OR |
| | EXISTING SMOKE ALARM DEVICES. |
| | 5) NOTE:ARC FAULT INDICATED ON PANEL SCHEDULE HOWEVER |
| | AS CIRCUITING IS NOT ON PLANS FOR NEW ITEMS, THIS CAN |
| | NOT BE VERIFIED. |
| | PLEASE SEE 210.12 AND LIST. |
| | |
| | 6) NOTE:THIS NOTE REMAINS AS WIRE SIZE AND OVER |
| | CURRENT PROTECTION ARE NOT SHOWN ON PANEL SCHEDULE. |
| | PLEASE ALSO SEE CIRCUITING ON PLANS. |
| | PLEASE BE SURE TO LIST THE REQUIRED DEDICATED |
| | CIRCUIT(S) FOR BATH RECEPTACLE(S) PER 210.52D, |
| | 210.11C3. |
| | (MUST BE 20AMP AND #12) |
| | |
| | 7) NOTE:THIS WAS NOTE #8 ON PREVIOUS REVIEW. |
| | PLEASE KNOW BEDRM #2 WILL REQUIRE SOME SORT OF LIGHT |
| | FIXTURE FOR EGRESS INTO THIS ROOM PER 210.70, LS 101 |
| | 7.8 |
| | |
| | 8) NOTE: THIS WAS NOTE #10 ON PREVIOUS REVIEW. |
| | PLEASE SEE MISSING DEDICATED LOAD FOR NEW REFRIGERATOR |
| | ON LOAD CALCULATIONS. |
| | 220. |
| | (LIST ON PANEL SCHEDULE). |
| | |
| | 9) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | REPEAT COMMENTS FOR CODE COMPLIANCE. |
| | THIS IS ONLY A NOTICE GIVEN AT THIS TIME. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |