2007-10-04 15:44:33*****DENIED*****
  
  
 1.THE ACTUAL ADDRESS OF THE PROJECT SITE SHALL BE IN
 THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.BE
 ADVISED THAT THIS RESIDENCE IS IN THE JURISDICTION OF
 WEST PALM BEACH, FLORIDA 33401.THE SUITE NUMBER SHOWN
 ON THE PLAN AS 15A DO NOT CORRELATE WITH WHAT IS
 INDICATED IN THE CITY'S PERMITTING SYSTEM WHICH IS
 1501.PLEASE CLARIFY OR AMEND.
  
 2.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 4.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE DAILY OR MORE FREQUENTLY AS
 NECESSARY FOR SAFE OPERATION.
  
 5.THE REMOVAL OF OLD AND/OR THE STOCKING OF NEW
 BUILDING MATERIALS & SUPPLIES SHALL NOT HINDER OR
 INTERFERE WITH ACCESS TO OR EGRESS FROM THE OTHER
 TENANT SPACES ON THE 15TH FLOOR OR THE BUILDING.
  
 6.PLEASE SHOW THE LOCATION OF THE SMOKE ALARMS (SA)
 IN THIS RESIDNCE.
  
 7.SPECIFY THE NEW INTERIOR WALL AND CEILING FINISH
 MATERIAL IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 8.PLEASE INDICATE IF THE BUILDING IS SPRINKLERED AND
 IF SO, WILL THE SCOPE WORK CAUSE ANY SPRINKLER
 MODIFICATIONS.BE ADVISED THAT SEPARATE PLANS AND
 PERMIT WILL BE REQUIRED FOR SPRINKLER SYSTEM REMODEL.
  
 9.PLEASE INDICATE IF THE BUILDING/RESIDENCE HAS A
 FIRE ALARM SYSTEM AND IF SO, WILL THE SCOPE OF WORK
 CAUSE ANY FIRE ALARM DEVICE(S) MODIFICATIONS.BE
 ADVISED THAT SEPARATE PLANS AND PERMIT WILL BE REQUIRED
 FOR THE FIRE ALARM REMODEL.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722