| Date |
Text |
| 2007-09-15 11:55:50 | 2007-09-15 11:55:50 |
| | |
| | ** DENIED ** |
| | |
| | 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS |
| | WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES |
| | PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | 2) NOTE: PLEASE SEE NO DESIGN PROFESSIONAL IS PRINTED, |
| | SIGNED, OR SIGNED, DATED AND SEALED ON PLANS. PLEASE |
| | SEE MISSING INFORMATION FOR TITLE BLOCKS IF DONE BY A |
| | DESIGN PROFESSIONAL UNDER FS 481, 471 PER FAC |
| | 61G15-23.002, 61G1-16.004. |
| | PLEASE KNOW EVEN WHEN MEETING ANY EXCEPTIONS UNDER FS |
| | 471.003, OR 481.229 A DESIGNER OF RECORD IS STILL |
| | REQUIRED TO PRINT NAME AND SIGN PLANS. |
| | FBC 106.1.2, 106.3, 106.5 |
| | |
| | 3) NOTE: PLEASE COMPLETE ALL CIRCUITING ON PLANS FOR |
| | NEW AND CORRELATE WITH A NEW REVISED PANEL SCHEDULE TO |
| | BE SUBMITTED. THE EXISTING CIRCUITS ONLY NEED BE SHOWN |
| | WITH AN *E*. |
| | PLEASE SEE THE PANEL SCHEDULE IS TO INDICATE ALL NEW |
| | DEDICATED CIRCUITS AS NOTED BELOW. |
| | FBC 106.3.5.4 |
| | 408.4,240.4,310.16,408.4 ETC |
| | |
| | 4) NOTE: PLEASE SEE MISSING SMOKE DETECTION DEVICES AS |
| | REQUIRED UNDER FBC R313, AND NFPA-72 11.5.1.1, 11.8.3. |
| | THE PLANS NEED TO SHOW NEW OR EXISTING SMOKE ALARM |
| | DEVICES. |
| | **210.12 IN NEXT COMMENT APPLIES ** |
| | |
| | 5) NOTE: PLEASE BE SURE TO LIST THE REQUIRED ARC FAULT |
| | PROTECTED CIRCUITS PER 210.12 OF THE 2005 NEC. |
| | |
| | 6) NOTE: PLEASE BE SURE TO LIST THE REQUIRED DEDICATED |
| | CIRCUIT(S) FOR BATH RECEPTACLE(S) PER 210.52D, |
| | 210.11C3. |
| | (MUST BE 20AMP AND #12) |
| | |
| | 7) NOTE: PLEASE SEE MISSING GFI PROTECTION FOR SPA |
| | TUB/JACUZZI TUB PER 680.71 |
| | (LIST ON PANEL SCHEDULE) |
| | |
| | 8) NOTE: PLEASE KNOW BEDRM #2 WILL REQUIRE SOME SORT OF |
| | LIGHT FIXTURE FOR EGRESS INTO THIS ROOM PER 210.70, LS |
| | 101 7.8 |
| | |
| | 9) NOTE: PLEASE KNOW THESE PLANS MAY BE REFERENCE FOR |
| | LOW VOLTAGE PERMITS; HOWEVER PLEASE KNOW THE LV PERMIT |
| | IS SEPARATE FROM THE ELECTRICAL PERMIT. (SPKRS, TV, AND |
| | PHONE MAY BE ON ONE LV PERMIT) |
| | THIS IS ONLY NOTED AT THIS TIME FOR INFORMATION SO THIS |
| | DOES NOT LEAD TO ANY CONFUSION AT A LATER DATE AT |
| | INSPECTION(S) TIME. |
| | |
| | 10) NOTE: PLEASE SEE MISSING DEDICATED LOAD FOR NEW |
| | REFRIGERATOR ON LOAD CALCULATIONS. |
| | 220. |
| | (LIST ON PANEL SCHEDULE). |
| | |
| | 11) NOTE: PLEASE REVISE UNIT/SUITE # ON PLANS TO |
| | CORRELATE WITH SUITE/UNIT # IN OUR SYSTEM AS SSIGNED |
| | ADDRESS. (UNIT 1501). |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |