 ** DENIED **
  
 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 2) NOTE: PLEASE SEE NO DESIGN PROFESSIONAL IS PRINTED,
 SIGNED, OR SIGNED, DATED AND SEALED ON PLANS. PLEASE
 SEE MISSING INFORMATION FOR TITLE BLOCKS IF DONE BY A
 DESIGN PROFESSIONAL UNDER FS 481, 471 PER FAC
 61G15-23.002, 61G1-16.004.
 PLEASE KNOW EVEN WHEN MEETING ANY EXCEPTIONS UNDER FS
 471.003, OR 481.229 A DESIGNER OF RECORD IS STILL
 REQUIRED TO PRINT NAME AND SIGN PLANS.
 FBC 106.1.2, 106.3, 106.5
  
 3) NOTE: PLEASE COMPLETE ALL CIRCUITING ON PLANS FOR
 NEW AND CORRELATE WITH A NEW REVISED PANEL SCHEDULE TO
 BE SUBMITTED. THE EXISTING CIRCUITS ONLY NEED BE SHOWN
 WITH AN *E*.
 PLEASE SEE THE PANEL SCHEDULE IS TO INDICATE ALL NEW
 DEDICATED CIRCUITS AS NOTED BELOW.
 FBC 106.3.5.4
 408.4,240.4,310.16,408.4 ETC
  
 4) NOTE: PLEASE SEE MISSING SMOKE DETECTION DEVICES AS
 REQUIRED UNDER FBC R313, AND NFPA-72 11.5.1.1, 11.8.3.
 THE PLANS NEED TO SHOW NEW OR EXISTING SMOKE ALARM
 DEVICES.
 **210.12 IN NEXT COMMENT APPLIES **
  
 5) NOTE: PLEASE BE SURE TO LIST THE REQUIRED ARC FAULT
 PROTECTED CIRCUITS PER 210.12 OF THE 2005 NEC.
  
 6) NOTE: PLEASE BE SURE TO LIST THE REQUIRED DEDICATED
 CIRCUIT(S) FOR BATH RECEPTACLE(S) PER 210.52D,
 210.11C3.
 (MUST BE 20AMP AND #12)
  
 7) NOTE: PLEASE SEE MISSING GFI PROTECTION FOR SPA
 TUB/JACUZZI TUB PER 680.71
 (LIST ON PANEL SCHEDULE)
  
 8) NOTE: PLEASE KNOW BEDRM #2 WILL REQUIRE SOME SORT OF
 LIGHT FIXTURE FOR EGRESS INTO THIS ROOM PER 210.70, LS
 101 7.8
  
 9) NOTE: PLEASE KNOW THESE PLANS MAY BE REFERENCE FOR
 LOW VOLTAGE PERMITS; HOWEVER PLEASE KNOW THE LV PERMIT
 IS SEPARATE FROM THE ELECTRICAL PERMIT. (SPKRS, TV, AND
 PHONE MAY BE ON ONE LV PERMIT)
 THIS IS ONLY NOTED AT THIS TIME FOR INFORMATION SO THIS
 DOES NOT LEAD TO ANY CONFUSION AT A LATER DATE AT
 INSPECTION(S) TIME.
  
 10) NOTE: PLEASE SEE MISSING DEDICATED LOAD FOR NEW
 REFRIGERATOR ON LOAD CALCULATIONS.
 220.
 (LIST ON PANEL SCHEDULE).
  
 11) NOTE: PLEASE REVISE UNIT/SUITE # ON PLANS TO
 CORRELATE WITH SUITE/UNIT # IN OUR SYSTEM AS SSIGNED
 ADDRESS. (UNIT 1501).
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  