Plan Review Notes
Plan Review Notes For Permit 07090320
Permit Number 07090320
Review Stop E
Sequence Number 2
Notes
Date Text
2007-10-26 09:06:23 
  
  
  
 *** DENIED 2ND REVIEW ***
  
 1) NOTE: PLEASE SEE THE LIGHTING ENERGY CALCULATIONS
 SUBMITTED ATTACHED TO PLANS INDICATE A METHOD *C* AND
 METHOD AS SHOWN ON PLANS IS SPACE BY SPACE BY SPACE
 METHOD *B*.
 THIS SPACE IS BEING SHOWN AS *RETAIL* IN THE
 CALCULATIONS, HOWEVER BY DEFINITIONS IN THE FBC FOR
 OCCUPANCIES, THE AREA IS BASED AS A BUSINESS OCCUPANCY.
 THE CLOSEST SPACE WOULD BE OFFICE. THERE ARE ADDITIONAL
 WATTAGES PERMITTED FOR SOME ITEM AS LISTED IN
 13-415.2.B.1, HOWEVER THE WATTAGE AS SHOWN ON PLANS
 EXCEEDS THAT AS PERMITTED.
 PLEASE ADJUST FIXTURES/CALCULATIONS. PLEASE PROVIDE A
 MORE DETAIL BREAKDOWN FOR ANY ADDITIONAL WATTAGE AS
 PERMITTED. BASED ON THE WATTAGES SHOWN THESE DO NOT
 MEET 13-415.2, TABLES *B* OR *C*.
 PLEASE CALL TO GO OVER.
  
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH.
 561-805-6717
 [email protected]