| Plan Review Notes For Permit 07090320 |
| Permit Number |
07090320 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-10-26 09:06:23 | | | | | | | | | | | | | *** DENIED 2ND REVIEW *** | | | | | | 1) NOTE: PLEASE SEE THE LIGHTING ENERGY CALCULATIONS | | | SUBMITTED ATTACHED TO PLANS INDICATE A METHOD *C* AND | | | METHOD AS SHOWN ON PLANS IS SPACE BY SPACE BY SPACE | | | METHOD *B*. | | | THIS SPACE IS BEING SHOWN AS *RETAIL* IN THE | | | CALCULATIONS, HOWEVER BY DEFINITIONS IN THE FBC FOR | | | OCCUPANCIES, THE AREA IS BASED AS A BUSINESS OCCUPANCY. | | | THE CLOSEST SPACE WOULD BE OFFICE. THERE ARE ADDITIONAL | | | WATTAGES PERMITTED FOR SOME ITEM AS LISTED IN | | | 13-415.2.B.1, HOWEVER THE WATTAGE AS SHOWN ON PLANS | | | EXCEEDS THAT AS PERMITTED. | | | PLEASE ADJUST FIXTURES/CALCULATIONS. PLEASE PROVIDE A | | | MORE DETAIL BREAKDOWN FOR ANY ADDITIONAL WATTAGE AS | | | PERMITTED. BASED ON THE WATTAGES SHOWN THESE DO NOT | | | MEET 13-415.2, TABLES *B* OR *C*. | | | PLEASE CALL TO GO OVER. | | | | | | | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH. | | | 561-805-6717 | | | [email protected] |
|