2007-10-02 09:18:06DENIED;
 1.LIST THE ALTERATION LEVEL, TO COMPLY WITH THE FBC
 EXISTING BUILDING CODE.
 2. BREAK SINK SHALL COMPLY WITH FBC BUILDING CHAPTER 11
 SECTIONS 11-4.24.1 THRU 11-4.24.7.
 11-4.24.2 HEIGHT
 11-4.24.3 KNEE CLEARANCE, (NO DOORS IN CLEAR
 FLOOR SPACE)
 11-4.24.4 SINK DEPTH 6 1/2" MAX
 11-4.24.5 CLEAR FLOOR SPACE, ( SHOW ON PLANS)
 11-4.24.6 RAP EXPOSED PIPES.
 11-4.24.7 FAUCET, SPEC TYPE TO BE USED ON
 PLANS.
 3. SIZE ALL PIPES ON THE SANITARY ISOMETRIC.
 4. WATER SEVICE IS NOT LARGE ENOUGH SEE FBC PLUMBING
 TABLE 603.1. TOTAL FU'S IS 30.
 5. DRESSING ROOM TO COMPLY WITH FBC BUILDING CHAPTER
 11, SECTION 11-4.35.2 THRU 11-4.35.5
 11-4.35.2 CLEAR FLOOR SPACE OK
 11-4.35.3 DOORS OK
 11-4.35.4 BENCH REQUIRED. ( SHOW DETAIL WITH
 ALL REQUIRED MEASUREMENTS)
 11-4.35.5 MIRROR REQUIRED. ( SHOW DETAIL)
 6. SHOW SIZE OF WATER HEATERON PLANS.
 7. SHOWTYPE OF THERMAL EXPANSION PER FBC PLUMBING
 SECTION607.3.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695