| Plan Review Notes For Permit 07090320 |
| Permit Number |
07090320 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-10-02 09:18:06 | DENIED; | | | 1.LIST THE ALTERATION LEVEL, TO COMPLY WITH THE FBC | | | EXISTING BUILDING CODE. | | | 2. BREAK SINK SHALL COMPLY WITH FBC BUILDING CHAPTER 11 | | | SECTIONS 11-4.24.1 THRU 11-4.24.7. | | | 11-4.24.2 HEIGHT | | | 11-4.24.3 KNEE CLEARANCE, (NO DOORS IN CLEAR | | | FLOOR SPACE) | | | 11-4.24.4 SINK DEPTH 6 1/2" MAX | | | 11-4.24.5 CLEAR FLOOR SPACE, ( SHOW ON PLANS) | | | 11-4.24.6 RAP EXPOSED PIPES. | | | 11-4.24.7 FAUCET, SPEC TYPE TO BE USED ON | | | PLANS. | | | 3. SIZE ALL PIPES ON THE SANITARY ISOMETRIC. | | | 4. WATER SEVICE IS NOT LARGE ENOUGH SEE FBC PLUMBING | | | TABLE 603.1. TOTAL FU'S IS 30. | | | 5. DRESSING ROOM TO COMPLY WITH FBC BUILDING CHAPTER | | | 11, SECTION 11-4.35.2 THRU 11-4.35.5 | | | 11-4.35.2 CLEAR FLOOR SPACE OK | | | 11-4.35.3 DOORS OK | | | 11-4.35.4 BENCH REQUIRED. ( SHOW DETAIL WITH | | | ALL REQUIRED MEASUREMENTS) | | | 11-4.35.5 MIRROR REQUIRED. ( SHOW DETAIL) | | | 6. SHOW SIZE OF WATER HEATERON PLANS. | | | 7. SHOWTYPE OF THERMAL EXPANSION PER FBC PLUMBING | | | SECTION607.3. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|