2007-09-17 11:50:32PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) NEED TO SHOW ON MECHANICAL PLANS PAGE M1 THE SUPPLY
 AIR CFM'S AT THE GRILL OVER STYLING "B".
  
 2) SHOW RETURN AIR GRILLS ON MECHANICAL PLANS TO COMPLY
 WITH MECH. 601.4.
  
 4) PLEASE CHECK AND STATE (CODE WISE) WHERE THE OUTDOOR
 AIR CALCULATIONS ARE FROM ON PLAN ME1. SEE MECH. TABLE
 403.3 FOR BEAUTY SHOP AND NAIL SALON. 25 PERSONS PER
 1000 SQUARE FEET 2500 SQ.FT. / 1000 =2.5 X 25 =62.5
 PERSONS AT 25 CFM'S EACH =1562.5. AND YOU MAY ALSO
 CALCULATE NAIL SALON AT 4 SEATS X 25 CFM'S =100 CFM'S.
 ALSO SEE MECH. 403.3 THE OCCUPANT LOAD UTILIZED FOR
 DESIGN OF THE VENTILATION SYSTEM SHALL NOT BE LESS THAN
 THE NUMBER DETERMINED FROM THE ESTIMATED MAXIMUM
 OCCUPANT LOAD RATE INDICATED IN TABLE 403.3 .
  
 ** 403.4 ASHRAE 62 ALTERNATIVE.IN LIEU OF COMPLIANCE
 WITH SECTION 403.1 THROUGH SECTION 403.3 , MECHANICAL
 VENTILATION MAY BE IMPLEMENTED IN COMPLIANCE WITH
 ASHRAE 62 INCLUDING APPROVED ADDENDA.
  