| 2007-09-17 11:50:32 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST |
| | PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| | (F.S.). |
| | |
| | *** DENIED *** |
| | 1) NEED TO SHOW ON MECHANICAL PLANS PAGE M1 THE SUPPLY |
| | AIR CFM'S AT THE GRILL OVER STYLING "B". |
| | |
| | 2) SHOW RETURN AIR GRILLS ON MECHANICAL PLANS TO COMPLY |
| | WITH MECH. 601.4. |
| | |
| | 4) PLEASE CHECK AND STATE (CODE WISE) WHERE THE OUTDOOR |
| | AIR CALCULATIONS ARE FROM ON PLAN ME1. SEE MECH. TABLE |
| | 403.3 FOR BEAUTY SHOP AND NAIL SALON. 25 PERSONS PER |
| | 1000 SQUARE FEET 2500 SQ.FT. / 1000 =2.5 X 25 =62.5 |
| | PERSONS AT 25 CFM'S EACH =1562.5. AND YOU MAY ALSO |
| | CALCULATE NAIL SALON AT 4 SEATS X 25 CFM'S =100 CFM'S. |
| | ALSO SEE MECH. 403.3 THE OCCUPANT LOAD UTILIZED FOR |
| | DESIGN OF THE VENTILATION SYSTEM SHALL NOT BE LESS THAN |
| | THE NUMBER DETERMINED FROM THE ESTIMATED MAXIMUM |
| | OCCUPANT LOAD RATE INDICATED IN TABLE 403.3 . |
| | |
| | ** 403.4 ASHRAE 62 ALTERNATIVE.IN LIEU OF COMPLIANCE |
| | WITH SECTION 403.1 THROUGH SECTION 403.3 , MECHANICAL |
| | VENTILATION MAY BE IMPLEMENTED IN COMPLIANCE WITH |
| | ASHRAE 62 INCLUDING APPROVED ADDENDA. |
| | |