Plan Review Notes
Plan Review Notes For Permit 07090320
Permit Number 07090320
Review Stop E
Sequence Number 1
Notes
Date Text
2007-09-15 11:26:152007-09-15 11:26:15
  
 ** DENIED **
  
 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 2) NOTE: PLEASE COMPLETE ALL CIRCUITING ON PLANS AS
 THERE ARE SOME LIGHTING FIXTURES WHICH DO NOT SHOW
 CIRCUITING OR CONTROLS.
 FBC 106.3.5.4
 240.4,310.16,408.4 ETC
  
 3) NOTE: PLEASE SUBMIT A FIXTURE LEGEND, INCLUDING
 INFORMATION FOR NEW AND EXISTING FIXTURES.
 PLEASE SEE 13-415.2, 13-415.1.C.
 PLEASE SEE THE LIGHTING LEVELS FOR TRACK LIGHTING IS
 REQUIRED TO MEET 13-415.2.ABC.1.1, 13-415.2.ABC.1.2.
 (SEE PARAGRAPH (3) FOR LINE VOLTAGE TRACK).
 THIS IS REQUIRED TO BE THE LARGER OF THE LOADS BASED ON
 LINEAR FEET OF TRACK OR FIXTURE WATTAGE WHICH EVER IS
 GREATER.
 THE WATTAGE ON TRACK FIXTURES SEEM LOW, HOWEVER IN
 EITHER CASE THE LINEAR WATTAGE IS GREATER.
 PLEASE SE METHOD C AS SUBMITTED IS EXCEEDED FOR
 INTERIOR LIGHTING ALLOWANCES BASED ON PLANS AND
 LIGHTING AS SUBMITTED.
  
 4) NOTE: PLEASE SEE NO LIGHTING CONTROLS AS REQUIRED
 PER 13-415.1.ABC.1.1, .1.2 AND .1.3 IS SUBMITTED. THE
 PLANS INDICATE SOME SORT OF LIGHTING CONTACTOR LOCATED
 BY THE PANEL HOWEVER DEVICES, OVER RIDES, TIMES, OVER
 RIDE TIMES, ANY OCCUPANCY SENSORS OR TIMER INFORMATION
 WERE SUBMITTED FOR REVIEW. 13-101.
  
 5) NOTE: PLEASE SEE MISSING WINDOW RECEPTACLES WHICH
 WILL BE REQUIRED PER 210.62, 90.4 AND LOADS PER
 220.43.
  
 6) NOTE: PLEASE SEE TRACK LIGHTING CALCULATIONS ON LOAD
 CALCULATIONS NEED TO BE SHOWN PER 220.43.
  
 7) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING
 CONDUCTOR FROM MAIN DISCONNECT TO THE NEW SUB PANEL *B*
 AND FROM *B* TO *C*.
 250.110, 250.24, 250.122, ETC
  
 8) NOTE: RISER INDICATES NEW 300AMP SERVICE, WHAT IS
 THE SIZE OF THE EXISTING SERVICE FOR THIS SPACE? WHAT
 IS THE LOAD ON THE EXISTING SERVICE GUTTER CONDUCTORS
 WITH NEW LOAD NOW ADDED?
 NOT ENOUGH INFORMATION WAS GIVEN FOR NEW AND EXISTING
 LOADS.
 220, 240, 310.16, 215.5,
 FBC 106.3.5.1.2
  
 9) NOTE: PLEASE SEE 422.13 AS THE LOAD FOR WATER HEATER
 IS NOW CONSIDERED A CONTINUOUS LOAD UNDER THE 2005 NEC
 WHICH REQUIRES THIS LOAD TO BE SHOWN AT 125%.
  
 10) NOTE: PLEASE SEE 220.54 AND VERIFY LOAD FOR THE
 DRYER AS SHOWN. PLEASE SEE THIS IS BEING SHOWN ON A
 20AMP CIRCUIT WITH LOAD AT 19AMPS?
  
 11) NOTE: PLEASE SEE CIRCUITING ON PLANS NEEDS TO
 COORDINATE WITH THE PANEL SCHEDULES.
 PLEASE SEE THE DISPOSAL IS SHOWN TO CIRCUIT B-36,
 HOWEVER THIS IS THE SIGN CIRCUIT?
 FBC 106.1.2, 106.3.5.1.2,
 NEC 408.4
  
 12) NOTE: PLEASE SEE COMMENTS FROM BUILDING AND FIRE
 FOR ANY POSSIBLE HAZARDOUS CHEMICAL STORAGE/MIXING
 AREAS WHICH MAY BE OF CONCERN FOR LIFE SAFETY, ETC.
 THIS MAY AFFECT ELECTRICAL PLANS AND DESIGN IN
 GENERAL.
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  