| 2007-09-20 14:05:30 | BUILDING PLAN REVIEW |
| | PERMIT: 07090320 |
| | ADD: 1649 FORUM PLACE |
| | CONT: LONGMIRE BUILDING CORP. |
| | TEL: (561)753-3533 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW: 1ST |
| | ACTION: DENIED |
| | |
| | 1) - VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 2)110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION |
| | THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE |
| | OF OCCUPANCY: |
| | A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT IS |
| | DESIGNED. |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE |
| | PROVISIONS OF CHAPTER 3. |
| | C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6, |
| | TABLE 601. |
| | D) THE OCCUPANT LOAD, SEE 1004. |
| | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED |
| | F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED. |
| | G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE |
| | BUILDING PERMIT |
| | . ------------------------------------- |
| | ) NUMBER OF UNITS |
| | ) NUMBER OF FLOORS |
| | ) NUMBER OF ROOMS |
| | ) SQ. FT. FOOTPRINT |
| | |
| | 3)TABLE 803.5 MINIMUM INTERIOR FINISH CLASSIFICATION; |
| | PROVIDE INFORMATION BASED ON INTERIOR FINISH |
| | REQUIREMENTS BASED ON OCCUPANCY. |
| | |
| | |
| | |
| | 4)SINKS: |
| | 11-4.24.2 SINKS, HEIGHT. SINKS SHALL BE MOUNTED WITH |
| | THE COUNTER NO HIGHER THAN 34" ABOVE THE FINISH FLOOR. |
| | 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH |
| | 30" WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH |
| | SINKS. |
| | 11-4.24.5 CLEAR FLOOR SPACE. |
| | A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES |
| | (760 MM BY 1219 MM) COMPLYING WITH SECTION 11-4.2.4 |
| | SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW FORWARD |
| | APPROACH. THE CLEAR FLOOR SPACE SHALL BE ON AN |
| | ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM OF 19 |
| | INCHES (485 MM) UNDERNEATH THE SINK. THE DOORS IN FRONT |
| | OF THE SINK SHALL BE REMOVED TO PROVIDE THE FORWARD |
| | APPROACH. |
| | |
| | 5)2004 FBC EXISTING |
| | 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE |
| | OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO |
| | SECTIONS 303, 304 AND 305 OF THIS CODE. |
| | |
| | 6)SHEET 3.1. THE DRESSING ROOM SHALL HAVE A CLEAR |
| | FLOOR SPACE ALLOWING A PERSON USING A WHEELCHAIR TO |
| | MAKE A 180-DEGREE TURN. |
| | |
| | 7) SHEET 3.1. THE DRESSING ROOM SHALL HAVE 24 INCHES BY |
| | 48 INCHES BENCH FIXED TO THE WALL ALONG THE LONGER |
| | DIMENSION. THE BENCH SHALL BE MOUNTED 17 INCHES TO 19 |
| | INCHES ABOVE THE FINISH FLOOR. FBC 11-4.35.4. THE BENCH |
| | SHALL NOT PROJECT INTO THE CLEAR FLOOR SPACE. |
| | |
| | 8)THE RECEPTIONIST DESK SHALL MEET THE REQUIREMENTS |
| | OF FBC 11-7.2(2) (I). SHOW COMPLIANCE. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |
| | [email protected] |