| 2008-01-15 16:40:06 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | |
| | 1.THE WORK SPECIFIED IN THE ENGINEER'S LETTER IS NOT |
| | WITHIN THE SCOPE OF THE ROOFING CONTRACTOR'S LICENSE |
| | (STRUCTURAL REINFORCEMENT OF THE EXISTING ROOF RATERS). |
| | ATTEMPTS TO RESOLVE THIS ISSUE WITH THE CONTRACTOR OVER |
| | THE TELEPHONE WERE UNSUCCESSFUL AS THE CONTRACTOR |
| | WANTED TO YELL ABOUT LAST NIGHT'S COMMISSION MEETING |
| | RATHER THAN DISCUSS HOW I CAN ISSUE THIS REVISION AND |
| | WHAT OPTIONS ARE AVAILABLE. |
| | |
| | 2.THE ENGINEER'S LETTER MAKES REFERENCE TO A |
| | DIFFERENT PERMIT NUMBER AND ISLAND CONSTRUCTION.IF |
| | AGREEABLE TO ISLAND CONSTRUCTION, THE STRUCTURAL WORK |
| | CAN BE INCLUDED IN THEIR PERMIT WHEN ISSUED. |
| | ALTERNATIVELY, A CONTRACTOR LICENSED TO DO THE WORK CAN |
| | APPLY FOR A SUB PERMIT UNDER THIS ROOFING PERMIT. |
| | |
| | 3.AS THE REVISION CREATES AN ADDITIONAL DEAD LOAD ON |
| | THE STRUCTURE WHICH THE EXISTING STRUCTURE CANNOT |
| | ACCOMODATE (PER MESA ENGINEERING), THIS REVISION CANNOT |
| | BE ISSUED UNTIL THE STRUCTURAL ISSUE/PERMIT IS |
| | ADDRESSED. |
| | |
| | 4.FLORIDA STATE OR LOCAL PRODUCT APPROVALS REQUIRED, |
| | FAC9B72.THE LETTER MAKES REFERENCE TO MONIER CONCRETE |
| | TILE; PLEASE PROVIDE APPROPRIATE PRODUCT APPROVALS. |
| | |
| | 5.ON THE TILE PRODUCT APPROVAL, PLEASE MARK THE |
| | METHOD OF ATTACHMENT PROPOSED. |
| | |
| | |