| Plan Review Notes For Permit 07090304 |
| Permit Number |
07090304 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-09-13 13:57:20 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST | | | PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA | | | ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS). | | | | | | *** DENIED *** | | | 1) COOLING LOAD CALCULATIONS SHOW 872 SQUARE FEET OF | | | A/C SPACE, BUILDING PLANS ON FILE SHOW 1,197 SQUARE | | | FEET OF A/C SPACE. THE TWO MUST COINCIDE, PLEASE | | | RE-CALCULATE COOLING LOAD CAL'S. WITH THE CORRECT | | | SQUARE FEET OF COOLING SPACE. | | | | | | 2) AFTER RE-DOING COOLING LOAD CAL'S. CHECK THE A/C | | | EQUIPMENT LISTING ON THE PLANS FOR PROPER UNIT SIZE | | | (CORRECT LISTING IF NEEDED). | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|