2008-12-15 09:59:09REVISION DATED 12/8/08.
  
  
 1) SHEET FA-6 SCOPE OF WORK NOTE #5 SHOULD READ UL
 CERTIFICATED FOR CENTRAL STATION SERVICE.
  
 2) SHEET FA-6 FIRE ALARM NOTE # SHOULD READ GENERAL
 FIRE ALARM UPON ANY DUCT SMOKE DETECTOR ACTIVATION.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW