| Date |
Text |
| 2007-09-13 07:45:32 | |
| | ** DENIED ** |
| | |
| | 1) NOTE: PLEASE BE SURE TO STATE THE RELEVANT CODES ON |
| | PLANS |
| | 2004 FBC W/2006 REVISIONS. |
| | 2002 NFPA-72 |
| | 2005 NFPA-70 |
| | |
| | 2) NOTE: PLEASE SEE FBC RESIDENTIAL CODE R313 AS ANY |
| | NEW WORK IN UNIT IS REQUIRED TO HAVE THE SMOKE ALARMS |
| | BROUGHT UP TO CODE MEETING NFPA-72 11.5.1.1.1. IF THESE |
| | CURRENTLY ARE MEETING THE LATEST EDITION OF NFPA-72 |
| | PLEASE INDICATE THESE ON PLANS. |
| | |
| | 3) NOTE: PLEASE SEE NEC 210.12 FOR NEW INSTALLED FOR |
| | ARC FAULT PROTECTION. |
| | |
| | 4) NOTE: PLEASE SEE PLANS INDICATE NEW OVEN, COOK-TOP |
| | AND MICROWAVE HOWEVER NO INFORMATION ON THE ELECTRICAL |
| | IS SHOWN. WILL BE THIS BE NEW CIRCUITS, RECEPTACLES? IF |
| | SO, PLEASE SUBMIT A PANEL SCHEDULE WITH THE MINIMUM |
| | CONDUCTOR SIZES, OVER CURRENT PROTECTION AND EXISTING |
| | LOAD WITH NEW LOAD ON PANEL. |
| | IF THIS IS GOING TO BE FROM EXISTING CIRCUITS, PLEASE |
| | INDICATE. |
| | 408.4, 310.16, 240.4, |
| | FBC 106.3.5.4, 106.3.5.1.2, 106.1.2 |
| | |
| | 5) NOTE: PLEASE KNOW EVEN WHEN SCOPE OF WORK FALLS |
| | UNDER THE EXCEPTIONS OF 471 AND 481 OF THE FLORIDA |
| | STATUTES, THE SCOPE OF WORK STILL REQUIRES THE PLANS TO |
| | CONTAIN A PRINTED NAME AND SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR PLANS. |
| | PLEASE SEE FS 481.229 HOWEVER AS THE SCOPE OF WORK AS |
| | APPLIED WILL REQUIRE AN ARCHITECT AT A MINIMUM. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |