| 2007-11-03 11:13:25 | |
| | |
| | DENIED |
| | |
| | THE FOLLOWING COMMENTS WERE NOT ADDRESSED FROM 1ST |
| | REVIEW: |
| | |
| | 5)PROVIDE WIND DESIGN DATA ON DRAWINGS PER 1603.1.4 |
| | FBC |
| | *******NOTE WIND EXPOSURE NOT PRESENT ON |
| | DRAWING******* |
| | |
| | 6)SUBMIT TWO COPIES OF ENERGY CALC'S PER 13-101.2.2 |
| | FBC. BE SURE THAT THEY ARE SIGNED AND DATED BY PREPARER |
| | AND OWNER/AGENT PRIOR TO SUBMITTAL. |
| | ********NOTE THE ENERGY CALC'S DO NOT STATE THE AREA OF |
| | NEW WALL R19 INSULATION, THE EAVE OVERHANG SIZE FOR THE |
| | ADDITION IS INCORRECT AND THEY ARE NOT SIGNED BY THE |
| | OWNER/AGENT.******* |
| | |
| | 7)SUBMIT ENGINEERED TRUSS DRAWINGS THAT COMPLY WITH |
| | R802.10.1 FBC WITH PERMIT APPLICATION OR BEFORE |
| | INSTALLATION THAT HAVE BEEN REVIEWED AND APPROVED BY |
| | THE DESIGNER OF RECORD. DRAWINGS TO BE SIGNED AND |
| | SEALED BY TRUSS ENGINEER. |
| | *******NOTE COMPLETE ORIGINAL SIGNED AND SEALED TRUSS |
| | DRAWINGS WILL BE REQUIRED FOR SITE INSPECTOR BEFORE |
| | INSPECTION******* |
| | |
| | 8)PROVIDE PRODUCT APPROVAL FOR WINDOW MULLIONS OR IF |
| | SEPARATED BY STRUCTURE PROVIDE DETAIL. |
| | *******NOTE NO PRODUCT APPROVALS WERE SUBMITTED FOR |
| | WINDOW MULLIONS******* |
| | |
| | 9)PRODUCT APPROVAL FOR THE HARDIPLANK SIDING REQUIRES |
| | HORIZONTAL FASTENING INTO WALL STUDS AT 16" O/C BUT |
| | WALL SECTION ON SHEET 2 SHOWS FRAMING AT 24" O/C |
| | ********NOTE DRAWINGS WERE NOT CHANGED TO REFLECT THE |
| | MAXIMUM SPACING OF THE FRAMING MEMBERS FOR THE SIDING |
| | PRODUCT OF 16" O/C******* |
| | |
| | 11)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE |
| | 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC* |
| | ********NOTE PRODUCT APPROVALS WERE NOT REVIEWED AND |
| | APPROVED BY THE PERSONS RESPONSIBLE FOR |
| | DRAWINGS******** |
| | |
| | REMOVE ALL OLD PAGES AND RESUBMIT 2 COMPLETE SETS OF |
| | NEW DRAWINGS AND INCLUDE 1 COPY OF THE OLD PAGES ONLY |
| | FOR REFERENCE, PLEASE DON NOT REMOVE SHEET WITH IMPACT |
| | FEE STAMP. |
| | |
| | NO NEW COMMENTS PENDING |
| | |