| 2007-09-29 15:31:46 | |
| | |
| | DENIED |
| | |
| | 1)PLANS AND SPECIFICATIONS DESIGN PARAMETERS SHALL |
| | COMPLY WITH THE 2004 FLORIDA BLDG CODE WITH 2006 |
| | AMENDMENTS PER 106.1.1 FBC* |
| | |
| | 2)IN AN EXISTING BUILDING WHERE ALTERATIONS ARE BEING |
| | MADE A DESIGN PROFESSIONAL MUST ELECT THE LEVEL OF |
| | ALTERATION PER 301.5 OF EXISTING BUILDING CODE AND |
| | STATE ALONG WITH THE TYPE OF CONSTRUCTION ON THE |
| | DRAWINGS |
| | |
| | 3)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS |
| | LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS |
| | AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST |
| | EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC |
| | (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES |
| | PER 108.3 FBC* |
| | |
| | 4)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON |
| | SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER |
| | ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE |
| | ADDED TO THE PERMIT APPLICATION FEE |
| | |
| | NOTE: FEES ARE DUE IN THE AMOUNT OF $179.53 FOR |
| | INCREASED VALUE AND STATE RADON FEES THIS AMOUNT IS |
| | REQUIRED TO BE PAID PRIOR TO FURTHER PLAN REVIEW |
| | |
| | 5)PROVIDE WIND DESIGN DATA ON DRAWINGS PER 1603.1.4 |
| | FBC |
| | |
| | 6)SUBMIT TWO COPIES OF ENERGY CALC'S PER 13-101.2.2 |
| | FBC. BE SURE THAT THEY ARE SIGNED AND DATED BY PREPARER |
| | AND OWNER/AGENT PRIOR TO SUBMITTAL. PLEASE NOTE THAT |
| | CEILING R-VALUE DOES NOT MATCH DRAWINGS |
| | |
| | 7)SUBMIT ENGINEERED TRUSS DRAWINGS THAT COMPLY WITH |
| | R802.10.1 FBC WITH PERMIT APPLICATION OR BEFORE |
| | INSTALLATION THAT HAVE BEEN REVIEWED AND APPROVED BY |
| | THE DESIGNER OF RECORD. DRAWINGS TO BE SIGNED AND |
| | SEALED BY TRUSS ENGINEER. |
| | |
| | 8)PROVIDE PRODUCT APPROVAL FOR WINDOW MULLIONS OR IF |
| | SEPARATED BY STRUCTURE PROVIDE DETAIL. |
| | |
| | 9)PRODUCT APPROVAL FOR THE HARDIPLANK SIDING REQUIRES |
| | HORIZONTAL FASTENING INTO WALL STUDS AT 16" O/C BUT |
| | WALL SECTION ON SHEET 2 SHOWS FRAMING AT 24" O/C |
| | |
| | 10)PRODUCT APPROVALS FOR PGT WINDOWS AND JELD-WEN |
| | DOOR REQUIRE CORRECTIONS, SEE NOTES ON THE PRODUCT |
| | APPROVALS. |
| | |
| | 11)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE |
| | 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC* |
| | |
| | 12)A RECORDED COPY OF THE NOTICE OF COMMENCEMENT IS |
| | REQUIRED PRIOR TO A PERMIT BEING ISSUED |
| | |
| | BLDG PLAN REVIEW |
| | ADRIAN MORSE |
| | 561-805-6716 |