| 2007-09-17 18:00:19 | PROJECT: 525 SOUTH FLAGLER DRIVE/#07090103 |
| | |
| | PROJECT DETAIL: EXTEND HOISTWAY OF ELEVATOR SHAFT |
| | |
| | PLAN REVIEW: |
| | |
| | 2004 FLORIDA EXISTING BUILDING CODE/ 2006 REVS. 2004 |
| | FLORIDA BUILDING CODE W/2006 REVS. |
| | CITY OF WPB ADMINISTRATIVE AMENDMENTS/2004 |
| | |
| | COMMENTS: |
| | |
| | 1) PLEASE INDICATE THE LEVEL OF ALTERATION OR |
| | COMBINATIONS IF APPLICABLE: |
| | |
| | 301.5 . A DESIGN PROFESSIONAL OR AN OWNER MUST |
| | ELECT ONE OR A COMBINATION OF |
| | LEVELS OF ALTERATION PURSUANT TO SECTION 303,304 & |
| | 305 OF THIS CODE. |
| | |
| | 2)) AS PER THE FBC 106.3.5, PLEASE PROVIDE THE |
| | FOLLOWING DATA: |
| | |
| | A) BUILDING CONSTRUCTION TYPE |
| | B) OCCUPANCY LOAD |
| | C) OCCUPANCY GROUP |
| | D) SPRINKLERED OR NON-SPRINKLERED. |
| | |
| | 3) PLEASE REVISE THE TITLE BLOCK TO CONFORM TO THE |
| | FOLLOWING: |
| | |
| | 61G1-16.004 TITLE BLOCK. |
| | |
| | A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR |
| | INTERIOR DESIGN DRAWINGS AND SPECIFICATION |
| | IDENTIFICATION SHEETS. THE TITLE BLOCK |
| | MUST, AT A MINIMUM, CONTAIN THE FOLLOWING INFORMATION: |
| | (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER. |
| | (2) FIRM LICENSE NUMBER. |
| | (3) NAME OR IDENTIFICATION OF PROJECT. |
| | (4) DATE PREPARED. |
| | (5) A SPACE FOR THE SIGNATURE AND DATED SEAL. |
| | (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING |
| | THE DOCUMENT. |
| | SPECIFIC AUTHORITY 481.2055 FS. LAW IMPLEMENTED |
| | 481.203(6), 481.203(8), 481.2131(1), |
| | 481.219(3),(4),(5), 481.221, |
| | 481.225(1)(E),(G), 481.2251(1)(H) FS. HISTORY? |
| | |
| | 4) PLEASE SUBMIT A SITE PLAN INDICATING AREAS OF |
| | PROPOSED WORK: |
| | |
| | FBC 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN |
| | UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS ARE |
| | PERMITTED TO BE SUBMITTED WHEN APPROVED BY THE BUILDING |
| | OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT |
| | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| | BY THE BUILDING OFFICIAL (SEE ALSO SECTION 106.3.5). |
| | |
| | 5) PLEASE DENOTE ON PLAN THE FOLLOWING: |
| | |
| | A.) SHOW ALL DEMOLITION WORK. |
| | B.) DETAILS ON NEW STAIR REINFORCING STEEL/EPOXY & |
| | EMBEDMENT INTO EXISTING |
| | C.) PLANTER EXTENSION DETAILS. |
| | D.) TIE BEAM/BEAM SCHEDULE. |
| | E.) EXISTING STRUCTURAL MEMBERS/NEW STRUCTURAL |
| | MEMBERS/DIMENSIONS |
| | AT HOISTWAY. |
| | |
| | 6) PLEASE DIMENSION THE WIDTH OF THE STAIRS. |
| | |
| | 7) PLEASE INDICATE EXISTING AND NEW ELEVATIONS |
| | |
| | 8) SUBMIT HANDRAIL/GUARDRAIL SHOP DRAWINGS. |
| | |
| | 9) PROVIDE STRUCTURAL CALCULATIONS: |
| | |
| | FEBC 607.4EXISTING STRUCTURAL MEMBERS. |
| | EXISTING STRUCTURAL COMPONENTS SUPPORTING ADDITIONAL |
| | EQUIPMENT OR SUBJECTED TO ADDITIONAL LOADS BASED ON |
| | FLORIDA BUILDING CODE, BUILDING, TABLES 1607.1 AND |
| | 1607.6 (HIGH-VELOCITY HURRICANE ZONES SHALL COMPLY WITH |
| | TABLE 1615 AND SECTION 1615.2) AS A RESULT OF A |
| | RECONFIGURATION OF SPACES SHALL COMPLY WITH SECTIONS |
| | 607.4.1 THROUGH 607.4.3. |
| | |
| | 607.4.1GRAVITY LOADS. |
| | EXISTING STRUCTURAL ELEMENTS SUPPORTING ANY ADDITIONAL |
| | GRAVITY LOADS AS A RESULT OF ADDITIONAL EQUIPMENT OR |
| | SPACE RECONFIGURATION SHALL COMPLY WITH THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | EXCEPTIONS: |
| | 1. STRUCTURAL ELEMENTS WHOSE STRESS IS NOT INCREASED BY |
| | MORE THAN 5 PERCENT. |
| | 2. BUILDINGS OF GROUP R OCCUPANCY WITH NOT MORE THAN |
| | FIVE DWELLING UNITS OR SLEEPING UNITS USED SOLELY FOR |
| | RESIDENTIAL PURPOSES WHERE THE EXISTING BUILDING AND |
| | ITS ALTERATION COMPLY WITH THE CONVENTIONAL LIGHT-FRAME |
| | CONSTRUCTION METHODS AS DEFINED IN CHAPTER 2. |
| | |
| | FBC 106.1 |
| | |
| | 106.1 SUBMITTAL DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS, SPECIAL INSPECTION AND |
| | STRUCTURAL OBSERVATION PROGRAMS, AND OTHER DATA SHALL |
| | BE SUBMITTED IN ONE OR MORE SETS WITH EACH APPLICATION |
| | FOR A PERMIT. THE CONSTRUCTION DOCUMENTS SHALL BE |
| | PREPARED BY A DESIGN PROFESSIONAL WHERE REQUIRED BY THE |
| | STATUTES. WHERE SPECIAL CONDITIONS EXIST, THE BUILDING |
| | OFFICIAL IS AUTHORIZED TO REQUIRE ADDITIONAL |
| | CONSTRUCTION DOCUMENTS TO BE PREPARED BY A DESIGN |
| | PROFESSIONAL. |
| | |
| | |
| | PLAN REVIEW: KEN CONRAD |
| | PHONE:561.805.6666 |
| | E-MAIL: [email protected] |
| | |
| | |