Plan Review Notes For Permit 07090086
Permit Number 07090086
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-09-27 12:50:08***DENIED***
  
 TWO (2) SETS OF PLANS WERE STAMPED HOWEVER THIS WRITER
 NOW REALIZES THAT THIS BUILDING MAY BE PROTECTED BY AN
 AUTOMATIC FIRE SPRINKLER SYSTEM. THIS INFORMATION
 SIGNIFICANTLY IMPACTS THIS REVIEW.
  
 1) IF BUILDING IS PROTECTED BY AN AUTOMATIC FIRE
 SPRINKLER SYSTEM, PLEASE ADVISE AND SHOW APPLICABLE
 EQUIPMENT ON PLANS.
  
 2) IF BUILDING IS PROTECTED BY AN AUTOMATIC FIRE
 SPRINKLER SYSTEM, THE FIRE ALARM SHALL BE UL CERTIFIED
 FOR CENTRAL STATION SERVICE.
  
 3) PLEASE INCLUDE A SEQUENCE OF OPERATION ON THE
 PLANS.
  
 4) PLEASE ILLUSTRATE MONITORING ON THE PANEL DIAGRAM.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756