Plan Review Notes
Plan Review Notes For Permit 07090045
Permit Number 07090045
Review Stop E
Sequence Number 5
Notes
Date Text
2008-01-08 10:18:38*** PROVISO ***
  
 ** PLEASE SEE ITEMS FROM PREVIOUS REVIEW ARE STILL IN
 NEED OF ADDRESSING.
  
  
  
 1) NOTE: PLEASE SEE PREVIOUS REVIEW WITH RESPECT TO THE
 NEW TANK-LESS WATER HEATER. PLEASE SEE THE MANUFACTURES
 SPECS/CUTS NOW SUBMITTED AS THIS UNIT IS 240V AND THE
 SERVICE IS 208V. 17250VA AT 208V IS ABOVE THE BRANCH
 CIRCUIT RATING ON PANEL SCHEDULE. THIS WAS GIVEN ON
 PREVIOUS REVIEW HOWEVER CIRCUIT WAS NOT ADJUSTED. THE
 MANUFACTURES SPECS/CUT SHEETS DO STATE 80AMPS FOR THE
 OVER CURRENT PROTECTION HOWEVER THIS IS AT THE 240V
 RATING OF THE EQUIPMENT.
 PLEASE SEE SERVICE IS 208V.
 PLEASE KNOW AS THIS IS A LISTED ITEM AT 240V IT MAY
 VERY WELL NOT BE RATED FOR 208V.
 THESE NEED TO BE ADJUSTED AND VERIFIED.
 240.4, 310.16, 110.3, 90.7
  
 2) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENT #6 WHICH
 MENTIONED THE MISSING EQUIPMENT GROUNDING CONDUCTORS
 AFTER THE FIRST MEANS OF DISCONNECT. IN FACT THE NOTE
 GAVE NOTICE THAT THE EQUIPMENT GROUNDING CONDUCTORS ARE
 *ONLY AFTER THE FIRST MEANS OF DISCONNECT*.
 PLEASE SEE RISER NOTES/SHOWS THEM BOTH BEFORE AND
 AFTER.
 THIS CAN BE RED-LINED FOR NO INSTALLATION OF THESE
 BEFORE MAINS. (FIRST MEANS OF DISCONNECT).
  
  
 ** PLEASE SUBMIT REVISIONS OR REVISED SPECS/CUT SHEETS
 BEFORE ROUGH.
 ** PLEASE BE SURE TO ADDRESS COMMENTS AND IF THERE ARE
 ANY QUESTIONS, PLEASE CONTACT THIS REVIEWER.
  